ABB i-bus
KNX
Device technology
SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 13
Operating and display elements
Programming button and LED (red)
For assignment of the physical address
U
N
OK LED (green)
ON: Bus voltage and mains voltage OK
LED I > I
max
(red)
ON: Short-circuit or overload
Bus current LEDs (7 x yellow)
ON: Indicates present bus current
Telegr. LED (yellow)
ON: Telegram traffic
Comm. error LED (yellow)
ON: Communication error on bus
Reset
button and LED (red)
ON: Line reset.
To reset the device, press the button until the
LED comes on. The line is disconnected from
the voltage supply for 20 seconds. The LED then
goes off again.
OFF: Reset is complete.
Degree of protection
IP 20
EN 60 529
Protection class
II
EN 61 140
Isolation category
Overvoltage category
Pollution degree
III under EN 60 664-1
2 under EN 60 664-1
Temperature range
Operation
Storage
Transport
-
5 °C…+45 °C
-25…+55 °C
-25…+70 °C
Ambient conditions
Maximum air humidity
93 %, no condensation allowed
Design
Modular installation device (MDRC)
Modular installation device, Pro
M
Main dimensions (H x W x D)
90 x 72 x 64.5 mm
Mounting width
4 x 18 mm modules
Mounting depth
64.5 mm
Mounting
On 35 mm mounting rail
EN 60 715
Mounting position
As required
Weight
Approx. 0.26 kg
Housing, color
Plastic housing, gray
Approvals
KNX under EN 50 090-1, -2
CE mark
In accordance with the EMC guideline and low
voltage guideline
Device type
Application
Maximum number of
communication objects
Maximum number of
group addresses
Maximum number
of associations
SV/S 30.320.2.1
SV/S 30.640.5.1
Power Supply, Diagnosis, 320mA/...*
Power Supply, Diagnosis, 640mA/...*
7
9
254
254
254
254
* … = current version number of the application
Summary of Contents for SU/S 30.640.1
Page 1: ... PRODUCT MANUAL ABB i bus KNX SV S KNX Power Supplies ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 32: ......
Page 34: ...ABB i bus KNX Appendix 32 2CDC501049D0201 Rev A SV S xx xxx x 1 Notes ...