RuggedCom RSG2100
*
Westermo FST208
Media converters:
*
RuggedCom RMC-100-MM
*
IMC McBasic MM1300
*
Allied Telesyn AT-MC302-20
More tested devices can be found on the ABB web site
http://www.abb.com/substationautomation.
4.1.
Features
SPA-ZC 402 has the following features:
*
IEC 61850 connectivity for IED with fibre optic SPA bus
*
Auxiliary power supply
*
Easy-to-use configuration tool for the IEC 61850 data mapping
*
Support of communication over TCP/IP
All relay data can be routed through SPA-ZC 402. The process data (status,
measurements and commands) is routed through the IEC 61850 bus and the rest of
the available data can be routed through SPA over TCP/IP.
Only one SPA client can be configured to poll SPA events from the
device. By default SPA-ZC 402 is configured to poll SPA events, then
it is not allowed to poll SPA events from another SPA client.
If the parallel IEC 61850 communication is configured for
RE_ 541/3/5 with two SPA-ZC 40x gateways, SPA event polls have to
be disabled in another gateway.
If the parallel IEC 61850 communication is configured for RE_ 541/3/5 with two
SPA-ZC 402 gateways, SPA event polls has to be disabled in another gateway.
18
SPA-ZC 402
SPA-ZC 402
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
1MRS755380