73
11.2.1.6.
Originator
Table 11.2.1.6.-1
Step position with transient indication
OriginatorType Definition
Attribute Name
AttributeType
Value/ Value Range
M/O/C
SPA-ZC 402/
Comments
orCat
ENUMERATED
not-supported | bay-
control | station-control |
remote-control |
automatic-bay |
automatic-station |
automatic-remote |
maintenance | process
M
Supported
orIdent
OCTET STRING64
M
Supported
Table 11.2.1.6.-2
Values for orCat
Value
Explanation
bay-control
Control operation issued from an operator using a client
located at bay level
station-control
Control operation issued from an operator using a client
located at station level
remote-control
Control operation from a remote operater outside the
substation (e.g. network control center)
automatic-bay
Control operation issued from an automatic function at bay
level
automatic-station
Control operation issued from an automatic function at station
level
automatic-remote
Control operation issued from an automatic function outside of
the substation
maintenance
Control operation issued from a maintenance / service tool
process
Status change occurred without control action (e.g. external
trip of a circuit breaker or failure inside the breaker)
11.2.1.7.
Unit definition
Table 11.2.1.7.-1
Unit
Unit Type Definition
Attribute Name
AttributeType
Value/ Value Range
M/O/C
SPA-ZC 402/
Comments
SIUnit
ENUMERATED
According to table in
Annex A
M
Supported
multiplier
ENUMERATED
According to table in
Annex A
O
Supported
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
SPA-ZC 402
SPA-ZC 402
1MRS755380