11.2.2.24.
Analogue setting (ASG)
Table 11.2.2.24.-1 defines the common data class of analogue setting.
Table 11.2.2.24.-1
Analogue setting (ASG)
ASG class
Attribute Name Attribute Type
FC
TrgOp
Value/ Value
range
M/O/C
SPA-ZC 402/
Comments
DataName
Inherited from Data Class (refer to IEC 61850-7-2)
Not Supported
DataAttribute
Setting
setMag
AnalogueValue
SP
AC_NSG_M
Not Supported
setMag
AnalogueValue
SG SE
AC_SG_M
Not Supported
Configuration, Description and Extension
units
Unit
CF
see Annex A
O
Not Supported
sVC
ScaledValue-
Config
CF
AC_SCAV
Not Supported
minVal
AnalogueValue
CF
O
Not Supported
maxVal
AnalogueValue
CF
O
Not Supported
stepSize
AnalogueValue
CF
1
…
(maxVal -
minVal)
O
Not Supported
d
VISIBLE
STRING255
DC
Text
O
Not Supported
CdcNs
VISIBLE
STRING255
EX
AC_DLNDA_M Not Supported
cdcName
VISIBLE
STRING255
EX
AC_DLNDA_M Not Supported
dataNs
VISIBLE
STRING255
EX
AC_DLN_M
Not Supported
11.2.2.25.
Setting curve (CURVE)
Table 11.2.2.25.-1 defines the common data class of setting curve.
Table 11.2.2.25.-1
Setting curve (CURVE)
ASG class
Attribute Name Attribute Type
FC
TrgOp
Value/ Value
range
M/O/C
SPA-ZC 402/
Comments
DataName
Inherited from Data Class (refer to IEC 61850-7-2)
Not Supported
DataAttribute
Setting
setCharact
ENUMERATED
SP
AC_NSG_M
Not Supported
setParA
FLOAT32
SP
AC_NSG_O
Not Supported
setParB
FLOAT32
SP
AC_NSG_O
Not Supported
setParC
FLOAT32
SP
AC_NSG_O
Not Supported
setParD
FLOAT32
SP
AC_NSG_O
Not Supported
setParE
FLOAT32
SP
AC_NSG_O
Not Supported
96
SPA-ZC 402
SPA-ZC 402
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
1MRS755380