63
9.
Maintenance and service
If the SPA-ZC 402 module or a part of it is found to be faulty, the normal service
operation is to replace the entire module.
For more details, refer to Section 13. Ordering information.
9.1.
LED indicators
Table 9.1.-1
LED indicators
LED
Color
State
Sequence
number
Description
Power
Green
On
Power on
Link LAN
Green
On
Indication for LAN link OK
RX LAN
Green
On
Indication for incoming LAN traffic
TX LAN
Green
On
Indication for outgoing LAN traffic
RX SPA
Green
On
Indication for incoming SPA traffic
TX SPA
Green
On
Indication for outgoing SPA traffic
DIAG
Green
Red
Off
Flashing
On
Flashing
On
Off
On
On
On
Off
Off
Flashing
1
2
3
4
5
6
Bootloader booting
Bootloader, missing boot image
Starting
OK, missing configuration
OK, configuration in use
Configuration error
Possible sequences are:
1
→
3
→
5
Normal situation
1
→
2
Missing boot image
1
→
3
→
4
Configuration file is missing
1
→
3
→
6
Configuration error
If configuration error is detected because of the mismatches in
downloaded the CID file, download a simpler configuration. Check
also the log file in SPA-ZC 402.
9.2.
Communication settings
SPA addresses in sAddr are not properly defined if
*
Diagnostic counter SPAReplyTimo increases constantly and SPAReplyData
remains 0 in the LD0.CDGGIO1 logical node. These diagnostic counters are
readable from the IEC 61850 client.
*
Quality of the data is INVALID.
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
SPA-ZC 402
SPA-ZC 402
1MRS755380
Summary of Contents for SPA-ZC 402
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 14: ...14 ...
Page 28: ...28 ...
Page 54: ...54 ...
Page 58: ...58 ...
Page 68: ...68 ...
Page 104: ...104 ...
Page 106: ...106 ...
Page 108: ...108 ...
Page 110: ...110 ...