IEC18000676 V1 EN-US
Figure 46: PCM600: Common Read
Common Read collects information from SAM600 system related to configuration,
parameters, sampled value streams and reconstruct the same in PCM600. Common Read will
not read the topology or the interconnection between the modules. The process is shown in
The following attribute values are validated when Common Read action is initiated from
PCM600:
•
Technical Key
•
Number of SAM600 modules
•
Type of SAM600 modules
•
Serial Number
•
Order of SAM600 modules
•
Interconnection between SAM600 modules
•
Configuration existence in SAM600 system
Section 6
1MRK 511 433-UEN B
Communication with PCM600 and SAM600 system
44
SAM600 Process Bus I/O System
Engineering manual
© Copyright 2017 ABB. All rights reserved