An error message is not displayed even when more than one PTP Access Point
per module is being saved in PST.
In a SAM600 system with multiple PTP Access Points, the transmitted PTP
traffic which is looped back to the system should be avoided.
•
Global parameters for a SAM600 system
Several settings like time synchronization related parameters need to be set in a
consistent way within a SAM600 system. Possible parameters are
Power System
Frequency and Time Synchronization Mode.
Global parameters can be set on a SAM600 system level where the specific parameter
settings are derived for the dependent SAM600 modules.
•
SAM600 module specific parameters
Module specific settings are set on a SAM600 module level. Possible parameters are
Transducer Values as parameters related to digital equation settings.
In addition there are some parameters appearing on both the levels. Parameter changes
on SAM600 system level are propagated to all SAM600 modules each time. Parameter
changes on SAM600 module level affects the related module parameters. Possible
parameters are
Trigger Levels for binary inputs and Active High or Active Low state for
binary inputs.
5.2
SAM600 SV stream and port configuration
GUID-004C1CD9-2BB5-4057-9039-52E162B78B93 v1
Sampled Value stream and Port Configuration is a tool used for merging the current and
voltage signals in a single IEC/UCA 61850-9-2LE stream and for defining the output. This is a
PCM600 tool which can be launched from a SAM600 system context menu, see
. It is
possible to subscribe external SV streams and to publish those over available SAM600 ports.
1MRK 511 433-UEN B
Section 5
SAM600 Engineering
SAM600 Process Bus I/O System
27
Engineering manual
© Copyright 2017 ABB. All rights reserved