9.
Click the Next button to open a SAM600 system Bus Port Selection Page.
10. Select the Custom Name from the drop-down list set in the previous page according to
the intended physical arrangement of a SAM600 system. After disposing the order of
modules by assigning the Custom Name, select the ports for a SAM600 system bus
connection between the Hardware Modules, see
.
IEC18000690 V1 EN-US
Figure 18: SAM600: Bus port selection page wizard
It is possible to configure a SAM600 system either as daisy chain or ring
system.
11.
Click the Next button to open a SAM600 system – Access Point Selection Page, see
12.
Right click on the page to create new Access Point. Select the redundancy Mode, Module
Name, Physical Port A, and Physical Port B (available if the redundancy Mode is either HSR
or PRP).
IEC18000691 V1 EN-US
Figure 19: SAM600: Access Point selection page wizard
Redundancy is supported only on SAM600-TS module and not on other
modules.
1MRK 511 433-UEN B
Section 4
Setting up a project
SAM600 Process Bus I/O System
21
Engineering manual
© Copyright 2017 ABB. All rights reserved