IEC18000684 V1 EN-US
Figure 16: PCM600: Product version selection wizard
If the selected Product Version is different, then an error message is
displayed.
7.
Click the Next button to open a SAM600 system — Composition Selection Page.
8.
Select the
Module Type and Hardware Type (available for SAM600-CT) from the
respective drop-down lists, also enter the
Serial Number and Custom Name in the
IEC18000689 V1 EN-US
Figure 17: PCM600: Composition selection page wizard
It is not mandatory to enter the Serial Number if not available at this
stage of the configuration phase. If required, modify the default Custom
name.
A SAM600 system consists of at least one module of any type (SAM600-
CT or SAM600-VT or SAM600-TS) and can have up to 10 SAM600 modules.
The amount of analog processing modules (SAM600-CT, SAM600-VT) per
SAM600 system is limited to 7. The amount of time synchronization
modules (SAM600-TS) is limited to 3 per SAM600 system.
Section 4
1MRK 511 433-UEN B
Setting up a project
20
SAM600 Process Bus I/O System
Engineering manual
© Copyright 2017 ABB. All rights reserved