Grid Automation Products

SAM600 Process Bus I/O System

Version 1.2

Engineering manual

Summary of Contents for SAM600 Series

Page 1: ...Grid Automation Products SAM600 Process Bus I O System Version 1 2 Engineering manual...

Page 2: ......

Page 3: ...Document ID 1MRK 511 433 UEN Issued May 2019 Revision B Product version 1 2 Copyright 2017 ABB All rights reserved...

Page 4: ...terms of such license Trademarks ABB and SAM600 are registered trademarks of the ABB Group All other brand or product names mentioned in this document may be trademarks or registered trademarks of the...

Page 5: ...roduct failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipme...

Page 6: ...0 EU and concerning electrical equipment for use within specified voltage limits Low voltage directive 2014 35 EU This conformity is the result of tests conducted by ABB in accordance with the product...

Page 7: ...h SAM600 product must be safely connected to ground using the ground strap Only a competent electrician is allowed to carry out the electrical installation Always follow national and local electrical...

Page 8: ......

Page 9: ...3 4 4 1 Configuration wizard 13 4 5 Inserting an SAM600 system in online mode 13 4 6 Inserting a SAM600 system in offline mode 18 4 6 1 Technical key 22 4 6 2 SAM600 serial numbers 24 Section 5 SAM600...

Page 10: ...41 6 2 Common read 43 Section 7 Event viewer tool 47 Section 8 IED configuration migration tool 49 8 1 Migration Procedure 49 8 1 1 Export and import of project 49 8 1 2 IED configuration migration I...

Page 11: ...and thorough knowledge of the specific communication protocol IEC 61850 1 3 Document revision history GUID DF73222C C15C 4961 B89A 0C30B78C8D12 v1 Document revision Date Product revision History A 20...

Page 12: ...to use a certain function Although warning hazards are related to personal injury it is necessary to understand that under certain operational conditions the operation of damaged equipment may result...

Page 13: ...T for further engineering The following data model changes are allowed by ICT according to IEC 61850 6 Edition 2 Addition of logical devices logical nodes or DATA within logical nodes Removal of logic...

Page 14: ...Upgrade Tool see Section 5 3 Configuring communication settings per SAM600 module such SAM600 system bus daisy chain or ring and IEC 61850 process bus communication redundancy configuration Configurin...

Page 15: ...Once the engineering of a SAM600 system is done the results are written to a SAM600 system Conversely engineering information can be uploaded from a SAM600 system for various purposes The connection b...

Page 16: ...8...

Page 17: ...are described in various sections throughout this document END Parametrization Sampled value and port configuration Write Configure the SAM600 IED by selecting the Hardware Modules selecting the port...

Page 18: ...10...

Page 19: ...kages install the required SAM600 system modules PCM600 version 2 8 Hot Fix 20180626 or newer must be used with SAM600 version 1 2 0 In the PCM600 Update Manager the Connectivity Package SAM600 system...

Page 20: ...name of each level in the structure should be renamed by the names or identifications used in the grid Use the right mouse button to build the plant structure by selecting the elements from the conte...

Page 21: ...hronized with the physical SAM600 system at a later state by connecting a SAM600 system to PCM600 and downloading the configuration The green check mark next to a SAM600 icon in Figure 4 indicates tha...

Page 22: ...e Configuration radio button See Figure 6 IEC18000109 V1 EN US Figure 6 PCM600 Configuration mode selection wizard 4 Select USB from the IED protocol drop down list see Figure 7 For SAM600 only USB IE...

Page 23: ...dicates the type of the physically connected SAM600 module IEC18000111 V1 EN US Figure 8 PCM600 Communication port selection wizard Only SAM600 USB connections that are available will be shown in the...

Page 24: ...0 is already configured then the topology information is fetched from the configuration on the SAM600 system If the SAM600 system is in factory default settings then the physical topology is discovere...

Page 25: ...Page see Figure 12 The dialog box displays Custom Name Module Type Hardware Type Serial Number and Available Access Points details It is possible to cancel the insertion using Cancel button or confirm...

Page 26: ...600 system in offline mode is similar to inserting an SAM600 system in online mode Follow the procedure to insert a SAM600 system in offline mode 1 Right click on the Bay navigate to New and select SA...

Page 27: ...mmunication port selection wizard In the offline mode it is not mandatory to select the USB port if not available at the engineering phase The selected port will be used later to write the configurati...

Page 28: ...PCM600 Composition selection page wizard It is not mandatory to enter the Serial Number if not available at this stage of the configuration phase If required modify the default Custom name A SAM600 sy...

Page 29: ...It is possible to configure a SAM600 system either as daisy chain or ring system 11 Click the Next button to open a SAM600 system Access Point Selection Page see Figure 19 12 Right click on the page t...

Page 30: ...ical key The purpose of the technical key is to prevent from writing a configuration to a wrong SAM600 system The technical key in SAM600 system and PCM600 must match to write the configuration Each S...

Page 31: ...22 PCM600 Technical key editor The following selections are possible using the Technical Key Editor Use the existing technical key in SAM600 system Use the existing technical key defined for a SAM600...

Page 32: ...mber of a SAM600 module is a global unique module identifier within the module type The serial numbers of SAM600 modules have to be entered before writing the configuration to a SAM600 system The seri...

Page 33: ...AM600 system are displayed in the IED Value field of PST see Figure 24 For more details see PCM600 online help Also the parameters in PCM600 can be modified using PST To export parameters from PST bot...

Page 34: ...e IC v Second ary nominal transducer value IC v Primary nominal transducer value IN v Second ary nominal transducer value IN v Neutral phase I PC Value I Unit I Min I Max A 50 Hz Calculated 110 voe Lo...

Page 35: ...ted to digital equation settings In addition there are some parameters appearing on both the levels Parameter changes on SAM600 system level are propagated to all SAM600 modules each time Parameter ch...

Page 36: ...n be modified if required Based on the hardware modules configured during a SAM600 system creation sample value streams lists the potential sources for currents and voltages SV streams can be added in...

Page 37: ...cting Voltage and or current modules for merging Define external SV Stream A SAM600 system has the capability to subscribe any external IEC UCA 61850 9 2LE sample value stream on any port Those extern...

Page 38: ...current and four voltage samples A SAM600 module cannot receive more than eight bridged streams either to a single port or to a different ports Port Assignment In the Destination Port assignment tab...

Page 39: ...0 to 9 and A to F For each destination port assignment of any SAM600 stream a new sample value control block will be instantiated For a SAM600 system with single module only three of the available fou...

Page 40: ...ration In case SAM600 modules are removed which are used to provide sample value information the respective configuration will be automatically updated The user will be informed and asked to confirm t...

Page 41: ...ubstation 2 Right click on the Substation and select Export The Export window appears 3 Select the location to store the SCD file with the required file name 4 Click the Save button The SCL Export Opt...

Page 42: ...0667 V1 EN US Figure 36 Export window Configured IED Description cid is used for the IEC 61850 structure as needed for a SAM600 system at runtime IED Capability Description icd is used for the IEC 618...

Page 43: ...se a System Tool will remove this subnetwork the SCD import will fail or be refused by PCM600 Follow the procedure to import an SCD file to PCM600 1 Select the Substation in the Plant Structure 2 Righ...

Page 44: ...e procedure to import an ICD or CID file to PCM600 1 Select the IED in the Plant Structure 2 Right click on the IED and select Import The Import window appears 3 Select the file to be imported from th...

Page 45: ...ossible to assign the serial number manually to the SAM600 module which is then assigned to the corresponding hardware module Validation errors to be taken care before the serial numbers are assigned...

Page 46: ...Mode When a SAM600 module is in simulation mode the respective hardware module in the PCM600 plant structure indicates this with orange coloring The quality of the effected streams will be set to good...

Page 47: ...ue The physical topology is retained as it is IEC18000674 V1 EN US Figure 42 PCM600 Reset to Factory Default 5 6 5 Indicate module GUID E62C6335 5B02 41A7 96CA 4E9498E22079 v1 Indicate Module action c...

Page 48: ...This command can also be launched from Get Serial Number tool Section 5 1MRK 511 433 UEN B SAM600 Engineering 40 SAM600 Process Bus I O System Engineering manual Copyright 2017 ABB All rights reserved...

Page 49: ...only through PCM600 and a physical connection to any SAM600 module in a SAM600 system is through USB see Figure 43 IEC18000116 V1 EN US Figure 43 SAM600 system communication with PCM600 6 1 Common wri...

Page 50: ...hnical Key Number of SAM600 modules Type of SAM600 modules Serial Number Order of SAM600 modules Interconnection between SAM600 modules The above mentioned attribute values are confirmed for the Commo...

Page 51: ...eration will not detect the newly added SAM600 module s It is advised to execute reset to factory default operation from the SAM600 system configuration context menu to identify all the modules in the...

Page 52: ...s is shown in the below flow chart see Figure 47 The following attribute values are validated when Common Read action is initiated from PCM600 Technical Key Number of SAM600 modules Type of SAM600 mod...

Page 53: ...art The above mentioned attribute values are confirmed for the Common Read to start If there are any discrepancies during the above validation common read is aborted and appropriate error message is d...

Page 54: ...46...

Page 55: ...igure 48 Event Viewer It is possible to set the number of events to be read from each SAM600 hardware module The value need to be set in the Read Event per Module property under Misc tab in the Object...

Page 56: ...48...

Page 57: ...8 1 1 Export and import of project GUID 687787FF 6310 42BD 842E 3BBD1EF86F3D v1 Before starting the migration ensure that correct version of PCM600 and SAM600 Connectivity Package Base are installed I...

Page 58: ...6F9 44C3 BD22 8F15C3E83F51 v1 1 Select the IED to migrate and right click migrate configuration 2 Select the version to migrate to e g 1 2 0 in the Dialog and press continue Section 8 1MRK 511 433 UEN...

Page 59: ...ted in the following screen and the migration process will take some minutes based on the configuration 5 At the end a dialog will confirm that the migration is completed 1MRK 511 433 UEN B Section 8...

Page 60: ...gration report can be either saved or printed later 6 The PCM600 output window will contain valuable information related to the migration Section 8 1MRK 511 433 UEN B IED configuration migration tool...

Page 61: ...Redundancy LE IEC UCA 61850 9 2LE Light Edition LED Light Emitted Diode MAC Media Access Control MSVCB Multicast Sample Value Control Block PCM600 Protection and Control IED Manager PRP IEC 62439 3 Pa...

Page 62: ...54...

Page 63: ...or current on the primary side of the measurement transformer For the SAM600 VT it is defined as the line line value Module Type SAM600 CT and SAM600 VT Level SAM600 Module Value Range SAM600 CT 1 65...

Page 64: ...l of the digital input channel 1 Module Type SAM600 CT and SAM600 VT Level SAM600 System can be re defined per SAM600 Module Value Range Low potential High potential Input disabled Default High potent...

Page 65: ...ype All Level SAM600 System Value Range Free running Pulse per second Grandmaster clock with GPS Master clock Default Free running Parameter IEEE1588 Domain Number Description The parameter defines th...

Page 66: ...fication Module Type All Level SAM600 Module Value Range String 10 First two characters are alphabets and remaining are 8 digits Default empty string Section 10 1MRK 511 433 UEN B SAM600 parameter set...

Page 67: ...59...