Climatic Operating Conditions
Section 3 Technical Data and Performance
116
3BSE015969-600 A
Climatic Operating Conditions
Table 14. Climatic Operating Conditions
Condition
Operative range
Standard
Temperature
(1)
(1) Approvals are issued for +5 to +55°C.
0 to +55°C non-condensing
0 to +40°C compact MTUs or S800L
modules on vertical DIN-rail, see
, non-condensing
IEC/EN 61131-2
Temperature
change
3 °C/min
Humidity
RH = 5 to 95%, no condensation
Altitude
2000 m
Pollution degree
Degree 2
IEC 60664-1
Corrosive
atmosphere
<1000 Angstrom copper corrosion over
28 days
<2000 Angstrom copper corrosion over
28 days
ISA-71.04
Severity level G2
ISA-71.04
Severity level G3
Mechanical Operating Conditions
Table 15. Mechanical Operating Conditions
Operative range
Standard
Vibration Test
Sinusoidal
Operational
5–9 Hz, amplitude 3,5 mm
9-150 Hz, acceleration 1,0g
1 octave/min
IEC/EN 61131-2
Shock
150 m/s
2
, 11 ms
IEC/EN 61131-2
Emitted noise
<55 dB (A)
Summary of Contents for S800
Page 1: ...Power and productivity for a better world S800 I O Product Guide ...
Page 2: ......
Page 3: ...S800 I O Product Guide ...
Page 8: ...Table of Contents 8 3BSE015969 600 A ...
Page 14: ...New in this Release About This Product Guide 14 3BSE015969 600 A ...
Page 16: ...16 3BSE015969 600 A Safety Summary ...
Page 97: ...Section 2 Product Description Power Supplies 3BSE015969 600 A 97 Figure 44 Voting Unit SS823 ...
Page 98: ...Power Supplies Section 2 Product Description 98 3BSE015969 600 A Figure 45 Voting Unit SS832 ...
Page 172: ...Certifications Section 3 Technical Data and Performance 172 3BSE015969 600 A ...
Page 174: ...Product and Price List Structure Section 4 Ordering 174 3BSE015969 600 A ...
Page 178: ...Appendix A Hardware Units for Essential Automation 178 3BSE020924 600 A ...
Page 182: ...Index 182 3BSE015969 600 A Index 182 3BSE015969 600 A ...
Page 184: ...Revision History 184 3BSE015969 600 A ...
Page 185: ......