Module Termination Unit
Section 2 Product Description
64
3BSE015969-600 A
Compact and Intrinsic Safety MTUs are 58mm (2.3”) wide, Extended MTUs are
120mm (4.72”) wide and Redundant MTUs are 124 mm (4.88”) wide. The MTU
types can be mixed and matched within an I/O station to fit a user’s needs. Choice of
MTU type can be made freely, trading space versus termination needs.
MTUs are available with rated insulation voltages 50 V and 250 V. The 50 V types
can be used with all 24/48 V discrete I/O and analog I/O modules. The MTUs with
250 V rated insulation voltage are used with all 120 V and 250 V rated I/O modules.
An inserted I/O module is assigned the unique position identity of its MTU.
Through the incremental bus design the physical size of an S800 I/O installation is
directly proportional to the number of installed MTUs.
The physical lock for S800 I/O which locks an I/O module to its MTU allows I/O
module removal only when the lock is in its unlocked position. The locking
mechanism also acts as a logic lock so that an I/O module is operable only when the
lock is in the locked position. If the lock is in its unlocked position, output channels
are de-energized and I/O modules can be inserted/removed without the need to
remove system or field power.
The S800 I/O modules can be inserted and removed from MTUs without
disturbing system operation.
Summary of Contents for S800
Page 1: ...Power and productivity for a better world S800 I O Product Guide ...
Page 2: ......
Page 3: ...S800 I O Product Guide ...
Page 8: ...Table of Contents 8 3BSE015969 600 A ...
Page 14: ...New in this Release About This Product Guide 14 3BSE015969 600 A ...
Page 16: ...16 3BSE015969 600 A Safety Summary ...
Page 97: ...Section 2 Product Description Power Supplies 3BSE015969 600 A 97 Figure 44 Voting Unit SS823 ...
Page 98: ...Power Supplies Section 2 Product Description 98 3BSE015969 600 A Figure 45 Voting Unit SS832 ...
Page 172: ...Certifications Section 3 Technical Data and Performance 172 3BSE015969 600 A ...
Page 174: ...Product and Price List Structure Section 4 Ordering 174 3BSE015969 600 A ...
Page 178: ...Appendix A Hardware Units for Essential Automation 178 3BSE020924 600 A ...
Page 182: ...Index 182 3BSE015969 600 A Index 182 3BSE015969 600 A ...
Page 184: ...Revision History 184 3BSE015969 600 A ...
Page 185: ......