The values in brackets are in Extended HART mode and HCIR.
In order to find out if a given configuration of analog and digital modules can be
used, the following method should be used:
•
Fill in number of modules in
•
Calculate the sum in the three columns:
–
Sum User Parameters
–
Sum Input Bytes
–
Sum Output Bytes
•
Calculate the three total sums for:
–
ParamSize
–
InSize
–
OutSize.
•
Check that:
–
ParamSize is less than or equal to 221 (220 if HCIR is used)
–
InSize is less than or equal to 239 in normal mode, 199 in Extended HART
mode
–
OutSize is less than or equal to 112 in normal mode, 90 in Extended
HART mode
If any of these three values is too high then the configuration can
not
be used.
DP840
7 (5)
Standard Drives
9 (7)
Table 24. Maximum Number of Modules on CI801 (Continued)
Module Type
Number of Modules
Summary of Contents for S800
Page 1: ...Power and productivity for a better world S800 I O Product Guide ...
Page 2: ......
Page 3: ...S800 I O Product Guide ...
Page 8: ...Table of Contents 8 3BSE015969 600 A ...
Page 14: ...New in this Release About This Product Guide 14 3BSE015969 600 A ...
Page 16: ...16 3BSE015969 600 A Safety Summary ...
Page 97: ...Section 2 Product Description Power Supplies 3BSE015969 600 A 97 Figure 44 Voting Unit SS823 ...
Page 98: ...Power Supplies Section 2 Product Description 98 3BSE015969 600 A Figure 45 Voting Unit SS832 ...
Page 172: ...Certifications Section 3 Technical Data and Performance 172 3BSE015969 600 A ...
Page 174: ...Product and Price List Structure Section 4 Ordering 174 3BSE015969 600 A ...
Page 178: ...Appendix A Hardware Units for Essential Automation 178 3BSE020924 600 A ...
Page 182: ...Index 182 3BSE015969 600 A Index 182 3BSE015969 600 A ...
Page 184: ...Revision History 184 3BSE015969 600 A ...
Page 185: ......