Section 3 Technical Data and Performance
Calculation of Maximum Distance of an Optical
3BSE015969-600 A
145
Calculation of Maximum Fiber length for TB826
The maximum signal delay in a configuration is calculated using Optical Media
Converter. This is calculated using the signal path from the controller to the point in
the configuration that has the longest delay. The maximum delay in a optical
ModuleBus configuration must be
100
µ
s (less than 250
µ
s for
S800 I/O HI).
The delay values in
can be used to calculate the maximum delay in an
optical ModuleBus configuration.
Table 30. Delay Values Optical ModuleBus Components
Opto-to-opto delay in TB826
(1)
(1) Notice that the delays in the table is the sum of the communication delay in both directions, i.e.
(delay of master frame) + (delay of slave frame).
2.0 µs
Opto-to-opto delay in TB820
4.0 µs
Opto-to-electrical delay in TB820
6.5 µs
Opto-to-opto delay in TB840
2.0 µs
Opto-to-electrical delay in TB840
5.5 µs
(2) Total fiber length = total local fiber field fiber length
(0.01 x length) µs
Summary of Contents for S800
Page 1: ...Power and productivity for a better world S800 I O Product Guide ...
Page 2: ......
Page 3: ...S800 I O Product Guide ...
Page 8: ...Table of Contents 8 3BSE015969 600 A ...
Page 14: ...New in this Release About This Product Guide 14 3BSE015969 600 A ...
Page 16: ...16 3BSE015969 600 A Safety Summary ...
Page 97: ...Section 2 Product Description Power Supplies 3BSE015969 600 A 97 Figure 44 Voting Unit SS823 ...
Page 98: ...Power Supplies Section 2 Product Description 98 3BSE015969 600 A Figure 45 Voting Unit SS832 ...
Page 172: ...Certifications Section 3 Technical Data and Performance 172 3BSE015969 600 A ...
Page 174: ...Product and Price List Structure Section 4 Ordering 174 3BSE015969 600 A ...
Page 178: ...Appendix A Hardware Units for Essential Automation 178 3BSE020924 600 A ...
Page 182: ...Index 182 3BSE015969 600 A Index 182 3BSE015969 600 A ...
Page 184: ...Revision History 184 3BSE015969 600 A ...
Page 185: ......