background image

APRIL  2019 REV.A

GFS-302

PAGE    1  of  4       

SERIES GL-RES

RESIDENTIAL PENDENT AND RECESSED PENDENT

K-FACTOR: 3.0, 4.1, 4.9, 5.6

4077 Airpark Dr. Standish, MI  48658 • 989-846-4583 • 

www.globesprinkler.com

Technical Support 

 989-414-2600

 

 

[email protected]

NOTE:

 

Users should refer to Globe’s web site (www.globesprinkler.com) 
to assure that the most recent technical literature is being utilized.

GENERAL DESCRIPTION

The series GL-RES pendent sprinklers are decorative fast 

response glass bulb sprinklers specifically tested and List

-

ed for use in residential applications such as homes, apart-

ments, hotels, and dormitories to provide control of these 

residential type fires and to improve the chance for occu

-

pants to escape. They utilize a 3mm frangible glass bulb as 

its heat sensing operating element. The recessed version 

of each of these Residential Sprinklers is intended for use 

in areas with finished ceilings. It employs a two-piece Re

-

cessed Escutcheon. The Recessed Escutcheon provides a 

total adjustment of 1/2 inch (12.7mm) from the flush ceiling 

position or ±1/4 inch (6.4mm) of recessed adjustment. The 

adjustment provided by the Recessed Escutcheon reduces 

the accuracy to which the pipe drops to the sprinklers must 

be cut.

This sprinkler may be installed within dwelling occupancies 

as allowed by NFPA 13, 13D, 13R and any other related 

documents as appropriate.

The GL3010 is typically utilized when maximum coverag

-

es  are  not  needed,  thereby  reducing  flow  demands.  The 

GL5610  is  typically  the  sprinkler  of  choice  when  utilizing 

Residential Sprinklers within an NFPA 13 Occupancy. The 

larger K-factor can be advantageous when needed to con-

form to the NFPA 13 hydraulic Special Design Approach for 

Residential Sprinklers.

OPERATION

Upon exposure to heat such as from a fire, the fluid in the 

bulb expands, compressing the air bubble within the bulb. 

When the air bubble can no longer compress, the fluid ex

-

pansion causes breakage of the glass bulb, resulting in re-

lease of the water seat assembly, and discharge of water 

from the sprinkler.

TECHNICAL DATA

Approvals

• 

See TABLE A

Maximum Working Pressure

• 

175 psi (12 bar)

Temperature Rating

• 

See TABLE A

K-Factor

• 

GL3010 K3.0 gpm/psi½    

(

43.2 lpm/bar½

)

• 

GL4110 K4.1 gpm/psi½    

(

59.0 lpm/bar½

)

• 

GL4910 K4.9 gpm/psi½    

(

70.6 lpm/bar½

)

• 

GL5610 K5.6 gpm/psi½    

(

80.6 lpm/bar½

)

Thread Size

• 

1/2” NPT (15 mm)

Length

• 

2-1/2” (6.3 cm)

Materials of Construction

• 

Frame - bronze 

 Deflector - brass 

 Screw - brass

• 

Lodgement Wire (GL5610 only) - stainless steel 

 Bulb  

seat - copper 

• 

Spring - nickel alloy 

 Seal - teflon

• 

Bulb - glass with alcohol based solution, 3mm

• 

Escutcheon Assembly - carbon steel 

FINISHES AND ACCESSORIES

Finishes

   

 Factory Bronze 

• 

Chrome 

 White Polyester 

   

 Black Polyester - 

special order

Escutcheons

   

 Brass 

• 

Chrome 

 White Polyester 

 Black Polyester

Wrenches

   •

 Standard 

• 

Recess 

 1/2” NPT

SERIES GL-RES

GL3010, GL4110, GL4910, GL5610

SERIES GL-RES RESIDENTIAL PENDENT AND RECESSED PENDENT 

K-FACTOR: 3.0, 4.1, 4.9, 5.6

SERIES GL-RES RESIDENTIAL PENDENT AND RECESSED PENDENT 

K-FACTOR: 3.0, 4.1, 4.9, 5.6

GFS-302

GFS-302

Summary of Contents for GL-RES Series

Page 1: ...FPA 13 13D 13R and any other related documents as appropriate The GL3010 is typically utilized when maximum coverag es are not needed thereby reducing flow demands The GL5610 is typically the sprinkler of choice when utilizing Residential Sprinklers within an NFPA 13 Occupancy The larger K factor can be advantageous when needed to con form to the NFPA 13 hydraulic Special Design Approach for Resid...

Page 2: ...the room or compartment using the area of the room divided by the number of sprinklers in the room 7psi minimum SIN K FACTOR GPM PSI lpm bar TEMPERATURE MAX AREA OF COVERAGE FEET m MINIMUM PRESSURE PSI bar MINIMUM FLOW GPM L min DEFLECTOR TO CEILING MOUNTING SURFACE DISTANCE INCHES mm MINIMUM DISTANCE BETWEEN SPRINKLERS FEET m 155 F 68 C 175 F 79 C 200 F 93 C GL3010 3 0 43 2 cULus EU 1 cULus cULus...

Page 3: ...e www globesprinkler com Always obtain permission from the proper authorities to shut down the affected fire protection system and notify all personnel who may be affected by this action before closing a fire protection system main control valve for maintenance work on the system that it controls Sprinklers should only be cleaned by means of gently dust ing with a feather duster otherwise non oper...

Page 4: ...VE CAPS SPRINKLER ESCUTCHEON Quantity Finish Part Number See TABLE C Quantity SIN Temperature Rating Finish Part Number See TABLE B TABLE B PART NUMBER SELECTION PART NUMBER SIN TEMPERATURE FINISH XXXX XXX XX SIN TEMPERATURE FINISH GL3010 3010 155 155 F 68 C 01 BRONZE GL4110 4110 175 175 F 79 C 02 CHROME GL4910 4910 200 200 F 93 C 03 WHITE POLYESTER GL5610 5610 04 BLACK POLYESTER Note All combinat...

Reviews: