Supervision functions

Table 62. Current circuit supervision (CCRDIF)

Characteristic

Value

Operate time

1)

< 30 ms

1)

Including the delay of the output contact.

Table 63. Current circuit supervision (CCRDIF) main settings

Parameter

Values (Range)

Unit

Description

Start value

0.05...0.20

x I

n

Minimum operate current
differential level

Maximum operate current

1.00...5.00

x I

n

Block of the function at
high phase current

Table 64. Fuse failure supervision (SEQRFUF)

Characteristic

Value

Operate time

1)

 

 

• NPS function

U

Fault

 = 1.1 x set 

Neg Seq

voltage Lev

< 33 ms

U

Fault

 = 5.0 x set 

Neg Seq

voltage Lev

< 18 ms

• Delta function

ΔU = 1.1 x set 

Voltage

change rate

< 30 ms

ΔU = 2.0 x set 

Voltage

change rate

< 24 ms

1)

Includes the delay of the signal output contact, f

n

 = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on

statistical distribution of 1000 measurements

Voltage Protection and Control

1MRS757058 D

REU615

 

Product version: 4.0

 
 

42

ABB

Summary of Contents for REU615

Page 1: ...Relion 615 series Voltage Protection and Control REU615 Product Guide...

Page 2: ...unit 45 23 Selection and ordering data 45 24 Accessories and ordering data 48 25 Tools 49 26 Terminal diagrams 51 27 References 53 28 Functions codes and symbols 54 29 Document revision history 56 Dis...

Page 3: ...ices Once the standard configuration IED has been given the application specific settings it can directly be put into service The 615 series IEDs support a range of communication protocols including I...

Page 4: ...3 Positive sequence undervoltage protection instance 1 Positive sequence undervoltage protection instance 2 Negative sequence overvoltage protection instance 1 Negative sequence overvoltage protectio...

Page 5: ...5 Disconnector position indication instance 3 5 5 Earthing switch indication instance 1 5 5 Earthing switch indication instance 2 5 5 Tap changer position indication Tap changer control with voltage...

Page 6: ...with optional hardware and software standard configuration A also features three light detection channels for arc fault detection in the metering cubicle or busbar compartment of metal enclosed switch...

Page 7: ...operate when the input values are below or exceeds the set values GUID 5E258DF3 B410 4FEE 9925 A8FC9C3617CE V2 EN Figure 1 Protection function overview of standard configuration A Voltage Protection a...

Page 8: ...s An integrated synchro check function ensures a synchronized connection of the equipment into the network In distribution networks containing distributed power generation REU615 can be used for loss...

Page 9: ...parts of the busbar Apart from the busbar protection and supervision the REU615 IED is utilized for centralized load shedding disconnection and restoration reconnection of one of the outgoing feeders...

Page 10: ...y configured via the PCM600 Protection and Control IED Manager and integrated with the Grid Automation controller COM600 or the MicroSCADA Pro network control and management system The 615 series IEDs...

Page 11: ...time and history values Better understanding of the process behaviour by joining time based process measurements with production and maintenance events helps the user in understanding the process dyn...

Page 12: ...on the chosen standard configuration Standard configuration A offers phase voltage residual voltage and voltage phase sequence component measurement In addition the standard configuration includes fre...

Page 13: ...to store the records of 128 latest fault events The records enable the user to analyze the power system events Each record includes current voltage and angle values time stamp etc The fault recording...

Page 14: ...s and the residual voltage input covers the rated voltages 60 210 V Both phase to phase voltages and phase to earth voltages can be connected The phase current input 1 A or 5 A the residual current in...

Page 15: ...bus inside of a switchgear bay The self healing Ethernet ring solution enables a cost efficient communication ring controlled by a managed switch with rapid spanning tree protocol RSTP support to be...

Page 16: ...hronization wiring IRIG B Inter Range Instrumentation Group Time Code Format B In addition the IED supports time synchronization via the following serial communication protocols Modbus DNP3 IEC 60870...

Page 17: ...Interfaces Protocols Ethernet Serial 100BASE TX RJ 45 100BASE FX LC RS 232 RS 485 Fibre optic ST IEC 61850 MODBUS RTU ASCII MODBUS TCP IP DNP3 serial DNP3 TCP IP IEC 60870 5 103 Supported Voltage Prot...

Page 18: ...uption time in the auxiliary DC voltage without resetting the IED 50 ms at Unrated Uauxvariation 38 110 of Un 38 264 V AC 50 120 of Un 12 72 V DC 80 120 of Un 38 4 300 V DC Start up threshold 19 2 V D...

Page 19: ...inputs Rated voltage 60 210 V AC Voltage withstand Continuous 240 V AC For 10 s 360 V AC Burden at rated voltage 0 05 VA 1 Residual current and or phase current Table 9 Binary inputs Description Valu...

Page 20: ...s RTD resistance sensing current Maximum 0 33 mA rms Operation accuracy Resistance Temperature 2 0 or 1 1 C 10 copper 2 C mA inputs Supported current range 0 20 mA Current input impedance 44 0 1 Oper...

Page 21: ...ed in series 5 A 3 A 1 A Minimum contact load 100 mA at 24 V AC DC Trip circuit supervision TCS Control voltage range 20 250 V AC DC Current drain through the supervision circuit 1 5 mA Minimum voltag...

Page 22: ...Table 18 Lens sensor and optical fibre for arc protection Description Value Fibre optic cable including lens 1 5 m 3 0 m or 5 0 m Normal service temperature range of the lens 40 100 C Maximum service...

Page 23: ...amp heat test 6 cycles 12 h 12 h at 25 C 55 C humidity 93 IEC 60068 2 30 Change of temperature test 5 cycles 3 h 3 h at 25 C 55 C IEC60068 2 14 Storage test 96 h at 40 C 96 h at 85 C IEC 60068 2 1 IEC...

Page 24: ...class III 10 V m rms f 80 2700 MHz IEC 61000 4 3 IEC 60255 22 3 class III 10 V m f 900 MHz ENV 50204 IEC 60255 22 3 class III 20 V m rms f 80 1000 MHz IEEE C37 90 2 2004 Fast transient disturbance tes...

Page 25: ...10 m distance 230 1000 MHz 47 dB V m quasi peak measured at 10 m distance Table 23 Insulation tests Description Type test value Reference Dielectric tests 2 kV 50 Hz 1 min 500 V 50 Hz 1 min communicat...

Page 26: ...7 2005 EN 60255 1 2009 Table 26 EMC compliance Description Reference EMC directive 2004 108 EC Standard EN 50263 2000 EN 60255 26 2007 Table 27 RoHS compliance Description Complies with RoHS directive...

Page 27: ...o Typical 0 96 Retardation time 30 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms 3 Suppr...

Page 28: ...on accuracy Depending on the frequency of the voltage measured fn 2 Hz 1 5 of the set value or 0 002 x Un Start time1 2 Minimum Typical Maximum UFault 1 1 x set Start value 22 ms 24 ms 26 ms Reset tim...

Page 29: ...me mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms3 Suppression of harmonics DFT 50 dB at f n x fn where n 2 3 4 5 1 Start value 1 0...

Page 30: ...ndervoltage protection PSPTUV main settings Parameter Function Value Range Step Start value PSPTUV 0 010 1 200 x Un 0 001 Operate delay time PSPTUV 40 120000 ms 10 Voltage block value PSPTUV 0 01 1 0...

Page 31: ...RPFRQ main settings Parameter Values Range Unit Step Default Description Operation mode 1 Freq 2 Freq 3 df dt 4 Freq df dt 5 Freq df dt 6 Freq OR df dt 7 Freq OR df dt 1 Freq Frequency protection oper...

Page 32: ...T2PTTR 6 60000 s 1 Current reference T2PTTR 0 05 4 00 x In 0 01 Operation T2PTTR Off On Table 42 Residual overvoltage protection ROVPTOV Characteristic Value Operation accuracy Depending on the freque...

Page 33: ...settings Parameter Function Value Range Step Phase start value Operating phase current ARCSARC 0 50 40 00 x In 0 01 Ground start value Operating residual current ARCSARC 0 05 8 00 x In 0 01 Operation...

Page 34: ...ettings Parameter Function Value Range Step Load shed mode LSHDPFRQ Freq Freq AND df dt Freq OR df dt Restore mode LSHDPFRQ Disabled Auto Manual Start value Freq LSHDPFRQ 0 800 1 200 x Fn 0 001 Start...

Page 35: ...EC Norm inv 10 IEC Very inv 11 IEC inv 12 IEC Ext inv 13 IEC S T inv 14 IEC L T inv 15 IEC Def Time 17 Programmable 18 RI type 19 RD type Operating curve type voltage protection 5 ANSI Def Time 15 IEC...

Page 36: ...equency of the voltage measured fn 1 Hz Voltage 3 0 of the set value or 0 01 x Un Frequency 10 mHz Phase angle 3 Reset time 50 ms Reset ratio Typical 0 96 Operate time accuracy in definite time mode 1...

Page 37: ...f 2 Synchronous 3 Asynchronous 2 Synchronous Synchrocheck operation mode Control mode 1 Continuous 2 Command 1 Continuous Selection of the synchrocheck command or continuous control mode Dead line val...

Page 38: ...sured fn 2 Hz Differential voltage Ud 0 5 of the measured value or 0 005 x Un in measured voltages 2 0 x Un Operation value 1 5 of the Ud for Us 1 0 x Un Operate time accuracy in definite time mode2 4...

Page 39: ...uto single Auto parallel Input control Delay characteristics OLATCC Inverse time Definite time LCT pulse time OLATCC 500 10000 ms 100 Band width voltage OLATCC 1 20 18 00 Un 0 01 Custom Man blocking O...

Page 40: ...f 0 01 4 00 x In Suppression of harmonics DFT 50 dB at f n x fn where n 2 3 4 5 Table 57 Three phase voltage measurement VMMXU Characteristic Value Operation accuracy Depending on the frequency of the...

Page 41: ...platinum 100 nickel 120 nickel 250 nickel 10 copper TCR 0 00385 DIN 43760 TCR 0 00385 TCR 0 00618 DIN 43760 TCR 0 00618 TCR 0 00618 TCR 0 00427 Supported resistance range 0 2 k Maximum lead resistanc...

Page 42: ...e function at high phase current Table 64 Fuse failure supervision SEQRFUF Characteristic Value Operate time1 NPS function UFault 1 1 x set Neg Seq voltage Lev 33 ms UFault 5 0 x set Neg Seq voltage L...

Page 43: ...ccessed using the web browser based user interface The default SLD can be modified according to user requirements by using the graphical display editor in PCM600 The local HMI includes a push button L...

Page 44: ...or two IEDs Alternatively the IED can be mounted in 19 instrument cabinets by means of 4U Combiflex equipment frames For the routine testing purposes the IED cases can be equipped with test switches t...

Page 45: ...IED including case with test switch wired and in stalled in a 19 equipment panel K 615 series IED including case with test switch wired and in stalled in a mounting bracket for CombiFlex rack mounting...

Page 46: ...ernet 100Base TX and FX 1 x RJ 45 2 x LC NE No communication module NN The communication module hardware determines the available communication proto cols Choose the hardware from one of the rows belo...

Page 47: ...a communication module cannot be combined with communication modules BN or BB B None N 15 Option 2 None N 16 Power supply 48 250 V DC 100 240 V AC 1 24 60 V DC 2 17 18 Version Version 4 0 XE H B U B C...

Page 48: ...18 test switch the test switch is not included in the delivery 2RCA021952A0003 19 rack mounting kit for one IED and one RTXP24 test switch the test switch is not included in the delivery 2RCA022561A00...

Page 49: ...browser based user interface is disabled by default The interface can be enabled with the PCM600 tool or from the front panel user interface The functionality of the interface can be limited to read...

Page 50: ...on management DNP3 communication configuration communication management IEC 60870 5 103 communication configuration communication management Saving of IED parameter settings in the tool Disturbance re...

Page 51: ...6 Terminal diagrams GUID B89BFFF3 08F0 40D3 8F12 99FB21B3900F V1 EN Figure 14 Terminal diagram of standard configuration A Voltage Protection and Control 1MRS757058 D REU615 Product version 4 0 ABB 51...

Page 52: ...GUID E5FA44B9 524F 4B19 A002 49D39DF6D6D5 V1 EN Figure 15 Terminal diagram of standard configuration B Voltage Protection and Control 1MRS757058 D REU615 Product version 4 0 52 ABB...

Page 53: ...he product page The download area on the right hand side of the web page contains the latest product documentation such as technical manual installation manual operation manual etc The Features and Ap...

Page 54: ...3 Three phase overvoltage protection PHPTOV1 3U 1 59 1 PHPTOV2 3U 2 59 2 PHPTOV3 3U 3 59 3 Positive sequence undervoltage protection PSPTUV1 U1 1 47U 1 PSPTUV2 U1 2 47U 2 Negative sequence overvoltage...

Page 55: ...ector position indication DCSXSWI1 I O DC 1 I O DC 1 DCSXSWI2 I O DC 2 I O DC 2 DCSXSWI3 I O DC 3 I O DC 3 Earthing switch indication ESSXSWI1 I O ES 1 I O ES 1 ESSXSWI2 I O ES 2 I O ES 2 Tap changer...

Page 56: ...ement PEMMXU1 P E P E RTD mA measurement XRGGIO130 X130 RTD X130 RTD Frequency measurement FMMXU1 f f 29 Document revision history Document revision date Product version History A 2010 06 11 3 0 First...

Page 57: ...57...

Page 58: ......

Page 59: ......

Page 60: ...Contact us ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41094 www abb com substationautomation 1MRS757058 D Copyright 2012 ABB All rights reserved...

Reviews: