Table 52. Synchronism and energizing check (SECRSYN) main settings, continued
Parameter
Values (Range)
Unit
Step
Default
Description
Maximum Syn
time
100...6000000
ms
10
2000
Maximum time to
accept
synchronizing
Energizing time
100...60000
ms
10
100
Time delay for
energizing check
Closing time of CB 40...250
ms
10
60
Closing time of
the breaker
Table 53. Tap changer control with voltage regulator (OLATCC)
Characteristic
Value
Operation accuracy
1)
Depending on the frequency of the current measured: f
n
±2 Hz
Differential voltage U
d
= ± 0.5% of the measured value or
± 0.005 x U
n
(in measured voltages < 2.0 x U
n
)
Operation value = ± 1.5% of the U
d
for Us = 1.0 x U
n
Operate time accuracy in definite time mode
2)
+ 4.0% / - 0% of the set value
Operate time accuracy in inverse time mode
2)
+ 8.5% / - 0% of the set value
(at theoretical B in range of 1.1…5.0)
Also note fixed minimum operate time (IDMT) 1 s.
Reset ratio for control operation
Reset ratio for analogue based blockings (except run
back raise voltage blocking)
Typical 0.80 (1.20)
Typical 0.96 (1.04)
1)
Default setting values used
2)
Voltage before deviation = set Band center voltage.
Voltage Protection and Control
1MRS757058 D
REU615
Product version: 4.0
38
ABB