Table 16. Station communication link, fibre-optic
Connector
Fibre type
1)
Wave length
Max. distance
Permitted path attenuation
2)
LC
MM 62.5/125 or 50/125
μm glass fibre core
1300 nm
2 km
<8 dB
ST
MM 62.5/125 or 50/125
μm glass fibre core
820-900 nm
1 km
<11 dB
1)
(MM) multi-mode fibre, (SM) single-mode fibre
2)
Maximum allowed attenuation caused by connectors and cable together
Table 17. IRIG-B
Description
Value
IRIG time code format
B004, B005
1)
Isolation
500V 1 min.
Modulation
Unmodulated
Logic level
TTL Level
Current consumption
2...4 mA
Power consumption
10...20 mW
1)
According to 200-04 IRIG -standard
Table 18. Lens sensor and optical fibre for arc protection
Description
Value
Fibre-optic cable including lens
1.5 m, 3.0 m or 5.0 m
Normal service temperature range of the lens
-40...+100°C
Maximum service temperature range of the lens, max 1 h
+140°C
Minimum permissible bending radius of the connection
fibre
100 mm
Table 19. Degree of protection of flush-mounted IED
Description
Value
Front side
IP 54
Rear side, connection terminals
IP 20
Table 20. Environmental conditions
Description
Value
Operating temperature range
-25...+55ºC (continuous)
Short-time service temperature range
Relative humidity
<93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
Up to 2000 m
Transport and storage temperature range
-40...+85ºC
Voltage Protection and Control