Table 34. Positive-sequence undervoltage protection (PSPTUV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 x U
n
Start time
1)2)
Minimum
Typical
Maximum
U
Fault
= 0.99 x set
Start
value
U
Fault
= 0.9 x set
Start value
51 ms
43 ms
53 ms
45 ms
54 ms
46 ms
Reset time
< 40 ms
Reset ratio
Depends of the set
Relative hysteresis
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n x f
n
, where n = 2, 3, 4, 5,…
1)
Start value = 1.0 x U
n
, Positive sequence voltage before fault = 1.1 x U
n
, f
n
= 50 Hz, positive sequence undervoltage with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
Table 35. Positive-sequence undervoltage protection (PSPTUV) main settings
Parameter
Function
Value (Range)
Step
Start value
PSPTUV
0.010...1.200 x U
n
0.001
Operate delay time
PSPTUV
40...120000 ms
10
Voltage block value
PSPTUV
0.01...1.0 x U
n
0.01
Table 36. Negative-sequence overvoltage protection (NSPTOV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
Minimum
Typical
Maximum
U
Fault
= 1.1 × set
Start value
U
Fault
= 2.0 × set
Start value
33 ms
24 ms
35 ms
26 ms
37 ms
28 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1)
Negative-sequence voltage before fault = 0.0 × U
n
, f
n
= 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase
angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
Voltage Protection and Control
1MRS757058 D
REU615
Product version: 4.0
30