Table 43. Residual overvoltage protection (ROVPTOV) main settings
Parameter
Function
Value (Range)
Step
Start value
ROVPTOV
0.010...1.000 x U
n
0.001
Operate delay time
ROVPTOV
40...300000 ms
1
Table 44. Arc protection (ARCSARC)
Characteristic
Value
Operation accuracy
±3% of the set value or ±0.01 x I
n
Operate time
Minimum
Typical
Maximum
Operation mode = "Light
only"
9 ms
10 ms
12 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Table 45. Arc protection (ARCSARC) main settings
Parameter
Function
Value (Range)
Step
Phase start value
(Operating phase current)
ARCSARC
0.50...40.00 x I
n
0.01
Ground start value
(Operating residual current)
ARCSARC
0.05...8.00 x I
n
0.01
Operation mode
ARCSARC
2=Light only
3=BI controlled
Table 46. Multipurpose protection (MAPGAPC)
Characteristic
Value
Operation accuracy
±1.0% of the set value or ±20 ms
Table 47. Multipurpose analog protection (MAPGAPC) main settings
Parameter
Function
Value (Range)
Step
Start value
MAPGAPC
-10000.0...10000.0
0.1
Operate delay time
MAPGAPC
0...200000 ms
100
Operation mode
MAPGAPC
Over
Under
-
Voltage Protection and Control
1MRS757058 D
REU615
Product version: 4.0
ABB
33
Summary of Contents for REU615
Page 1: ...Relion 615 series Voltage Protection and Control REU615 Product Guide...
Page 57: ...57...
Page 58: ......
Page 59: ......