Table 29. Three-phase non-directional overcurrent protection (PHxPTOC) main settings
Parameter
Function
Value (Range)
Step
Start Value
PHLPTOC
0.05...5.00 x I
n
0.01
PHHPTOC
0.10...40.00 x I
n
0.01
PHIPTOC
1.00...40.00 x I
n
0.01
Time multiplier
PHLPTOC
0.05...15.00
0.01
PHHPTOC
0.05...15.00
0.01
Operate delay time
PHLPTOC
40...200000 ms
10
PHHPTOC
40...200000 ms
10
PHIPTOC
20...200000 ms
10
Operating curve type
1)
PHLPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15,
17, 18, 19
PHHPTOC
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
PHIPTOC
Definite time
1)
For further reference please refer to the Operating characteristics table
Table 30. Three-phase overvoltage protection (PHPTOV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 x U
n
Start time
1)2)
Minimum
Typical
Maximum
U
Fault
= 1.1 x set
Start value
22 ms
24 ms
26 ms
Reset time
< 40 ms
Reset ratio
Depends of the set
Relative hysteresis
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50 dB at f = n x f
n
, where n = 2, 3, 4, 5,…
1)
Start value = 1.0 x U
n
, Voltage before fault = 0.9 x U
n
, f
n
= 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random
phase angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Maximum
Start value = 1.20 x U
n
,
Start value multiples in range of 1.10 to 2.00
Voltage Protection and Control
1MRS757058 D
REU615
Product version: 4.0