Table 52. Synchronism and energizing check (SECRSYN) main settings
Parameter
Values (Range)
Unit
Step
Default
Description
Live dead mode
-1=Off
1=Both Dead
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L Any
5=Dead L, Bus Any
6=One Live, Dead
7=Not Both Live
1=Both Dead
Energizing check
mode
Difference voltage 0.01...0.50
xUn
0.01
0.05
Maximum voltage
difference limit
Difference
frequency
0.001...0.100
xFn
0.001
0.001
Maximum
frequency
difference limit
Difference angle
5...90
deg
1
5
Maximum angle
difference limit
Synchrocheck
mode
1=Off
2=Synchronous
3=Asynchronous
2=Synchronous
Synchrocheck
operation mode
Control mode
1=Continuous
2=Command
1=Continuous
Selection of the
synchrocheck
command or
continuous
control mode
Dead line value
0.1...0.8
xUn
0.1
0.2
Voltage low-limit
line for energizing
check
Live line value
0.2...1.0
xUn
0.1
0.5
Voltage high-limit
line for energizing
check
Close pulse
200...60000
ms
10
200
Breaker-closing
pulse duration
Max energizing V
0.50...1.15
xUn
0.01
1.05
Maximum voltage
for energizing
Phase shift
-180...180
deg
1
180
Correction of
phase difference
between
measured
U_BUS and
U_LINE
Minimum Syn time 0...60000
ms
10
0
Minimum time to
accept
synchronizing
Voltage Protection and Control
1MRS757058 D
REU615
Product version: 4.0
ABB
37