![ABB Relion RER615 Modbus Point List Manual Download Page 74](http://html.mh-extra.com/html/abb/relion-rer615/relion-rer615_modbus-point-list-manual_2828074.webp)
2.4.34
LD0.PEMMTR1 Three-phase energy measurements (1)
Table 125:
LD0.PEMMTR1 Three-phase energy measurements (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.PEMMTR1
2037
u32
1
.SupWh.actVal
Reverse active energy (high)
0...1E10
[kWh]
2038
.SupWh.actVal
(low word)
2039
u32
1
.SupVArh.actVal
Reverse reactive energy (high)
0...1E10
[kVAr]
2040
.SupVArh.actVal
(low word)
2041
u32
1
.DemWh.actVal
Forward active energy (high)
0...1E10
[kWh]
2042
.DemWh.actVal
(low word)
2043
u32
1
.DemVArh.actVal
Forward reactive energy (high)
0...1E10
[kVAr]
2044
.DemVArh.actVal
(low word)
2.4.35
System diagnostic values
Table 126:
System diagnostic values
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.LPHD1
2050
u16
1
.PhyHealth1.stVal
Warning
Last warning code
1)
2051
u16
1
.PhyHealth2.stVal
Internal fault
Last internal fault code
1)
DR.RDRE1
2052
u16
1
.FltNum.stVal
Num.of DR recordings
0...N
2053
u16
1
.MemUsed.stVal
DR memory used
0...100 [%]
LD0.LPHD1
2054
u16
1
.NumPwrUp.stVal
Num of cold starts
0...65535
2055
u16
1
.WrmStr.stVal
Num of warm starts
0...65535
2056
u16
1
.WacTrg.stVal
Num of watchdog resets
0...65535
2057
u16
1
.NumCmpChg.stVal
Num of conf. changes
0...65535
1) See the technical manual.
Section 2
1MRS757822 B
Modbus data mappings
68
Recloser Protection and Control RER615
Point List Manual