2.3.64
LD0.MDSOPT1 Generic operation time supervision (1)
Since the register size is 16 bits, the value saturates at 65535 hours (approximately
7.5 years). Alternatively, a 32-bit user-definable register can be made of this data to
cover the whole 300 000 hours (34 years) range. The value can also, for example,
be rescaled to show “total operation days” instead by changing the scale factor
from 1 to 1/24 = 0.0417.
Table 67:
LD0.MDSOPT1 Generic operation time supervision (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.MDSOPT1
3308
205.12
OpTmWrn.stVal
WARNING
Op. time warning
1=Warning
3309
205.13
.mcd
3310
205.14
OpTmAlm.stVal
ALARM
Op. time alarm
1=Alarm
3311
205.15
.mcd
2.3.65
LD0.PHSVPR1 Voltage presence supervision (1)
Table 68:
LD0.PHSVPR1 Voltage presence supervision (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHSVPR1
3960
247.08
.VLiv.stVal
U_LIVE
High voltage presence
1=High voltage
3961
247.09
.mcd
3962
247.10
.VLivPhsA.stVal
U_A_AB_LIVE
High phsA or phsAB voltage
1=High voltage
3963
247.11
.mcd
3964
247.12
.VLivPhsB.stVal
U_B_BC_LIVE
High phsB or phsBC voltage
1=High voltage
3965
247.13
.mcd
3966
247.14
.VLivPhsC.stVal
U_C_CA_LIVE
High phsC or phsCA voltage
1=High voltage
3967
247.15
.mcd
3968
248.00
.VDea.stVal
U_DEAD
Low voltage presence
1=Low voltage
3969
248.01
.mcd
3970
248.02
.VDeaPhsA.stVal
U_A_AB_DEAD
Low phsA or phsAB voltage
1=Low voltage
3971
248.03
.mcd
3972
248.04
.VDeaPhsB.stVal
U_B_BC_DEAD
Low phsB or phsBC voltage
1=Low voltage
3973
248.05
.mcd
3974
248.06
.VDeaPhsC.stVal
U_C_CA_DEAD
Low phsC or phsCA voltage
1=Low voltage
3975
248.07
.mcd
Section 2
1MRS757822 B
Modbus data mappings
40
Recloser Protection and Control RER615
Point List Manual