![ABB Relion RER615 Modbus Point List Manual Download Page 57](http://html.mh-extra.com/html/abb/relion-rer615/relion-rer615_modbus-point-list-manual_2828057.webp)
BitA
RegA
IEC 61850 name
SA name
Description
Values
3187
199.03
.mcd
3188
199.04
.Ind3.stVal
X130-Input 3 State
0/1=Off/On
3189
199.05
.mcd
3190
199.06
.Ind4.stVal
X130-Input 4 State
0/1=Off/On
3191
199.07
.mcd
3192
199.08
.Ind5.stVal
X130-Input 5 State
0/1=Off/On
3193
199.09
.mcd
3194
199.10
.Ind6.stVal
X130-Input 6 State
0/1=Off/On
3195
199.11
.mcd
3264
204.00
.SPCSO1.stVal
X130-Output 1 State
0/1=Off/On
3265
204.01
.mcd
3266
204.02
.SPCSO2.stVal
X130-Output 2 State
0/1=Off/On
3267
204.03
.mcd
3268
204.04
.SPCSO3.stVal
X130-Output 3 State
0/1=Off/On
3269
204.05
.mcd
2.3.84
LD0.XGGIO120 Physical I/O states (AIM card X120)
Table 87:
LD0.XGGIO120 Physical I/O states (AIM card X120)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.XGGIO120
3200
200.00
.Ind1.stVal
X120-Input 1 State
0/1=Off/On
3201
200.01
.mcd
3202
200.02
.Ind2.stVal
X120-Input 2 State
0/1=Off/On
3203
200.03
.mcd
3204
200.04
.Ind3.stVal
X120-Input 3 State
0/1=Off/On
3205
200.05
.mcd
3206
200.06
.Ind4.stVal
X120-Input 4 State
0/1=Off/On
3207
200.07
.mcd
2.3.85
LD0.XGGIO110 Physical I/O states (BIO card X110)
Table 88:
LD0.XGGIO110 Physical I/O states (BIO card X110)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.XGGIO110
3216
201.00
.Ind1.stVal
X110-Input 1 State
0/1=Off/On
3217
201.01
.mcd
3218
201.02
.Ind2.stVal
X110-Input 2 State
0/1=Off/On
3219
201.03
.mcd
Table continues on next page
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
51
Point List Manual