![ABB Relion RER615 Modbus Point List Manual Download Page 56](http://html.mh-extra.com/html/abb/relion-rer615/relion-rer615_modbus-point-list-manual_2828056.webp)
2.3.80
CTRL.CBCSWI1 Circuit breaker (1) mom. position
Table 83:
CTRL.CBCSWI1 Circuit breaker (1) mom. position
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBCSWI1
POSITION
2804
175.04
.Pos.stVal.Close
-
Close bit
1=Close
2805
175.05
.Pos.stVal.Open
-
Open bit
1=Open
2806
175.06
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
2.3.81
CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
Table 84:
CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBCSWI1
POSITION
2816
176.00
.Pos.stVal.Close
Close bit
1=Close
2817
176.01
.mcd
2818
176.02
.Pos.stVal.Open
Open bit
1=Open
2819
176.03
.mcd
2820
176.04
< reserved >
2821
176.05
< reserved >
2822
176.06
.Pos.stSeld
SELECTED
CB selected for control
1=Selected
2823
176.07
.mcd
2.3.82
CTRL.CBCILO1 Circuit breaker (1) enable signals
Table 85:
CTRL.CBCILO1 Circuit breaker (1) enable signals
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBCILO1
2824
176.08
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
2825
176.09
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
2.3.83
LD0.XGGIO130 Physical I/O states (BIO card X130)
Table 86:
LD0.XGGIO130 Physical I/O states (BIO card X130)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.XGGIO130
3184
199.00
.Ind1.stVal
X130-Input 1 State
0/1=Off/On
3185
199.01
.mcd
3186
199.02
.Ind2.stVal
X130-Input 2 State
0/1=Off/On
Table continues on next page
Section 2
1MRS757822 B
Modbus data mappings
50
Recloser Protection and Control RER615