![ABB Relion RER615 Modbus Point List Manual Download Page 36](http://html.mh-extra.com/html/abb/relion-rer615/relion-rer615_modbus-point-list-manual_2828036.webp)
BitA
RegA
IEC 61850 name
SA name
Description
Values
3135
195.15
.mcd
3136
196.00
.Op.general
OPERATE
General operate
1=Operate
3137
196.01
.mcd
2.3.35
LD0.FRPFRQ1 Frequency protection (1)
Table 38:
LD0.FRPFRQ1 Frequency protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.FRPTRC1
4000
250.00
.Str.general
START
Stage 1 start
1=Start
4001
250.01
.mcd
LD0.FRPTOF1
Overfrequency
4002
250.02
.Op.general
OPR_OFRQ
Operate
1=Operate
4003
250.03
.mcd
LD0.FRPTUF1
Underfrequency
4004
250.04
.Op.general
OPR_UFRQ
Operate
1=Operate
4005
250.05
.mcd
LD0.FRPFRC1
Frequency gradient
4006
250.06
.Op.general
OPR_FRG
Operate
1=Operate
4007
250.07
.mcd
2.3.36
LD0.FRPFRQ2 Frequency protection (2)
Table 39:
LD0.FRPFRQ2 Frequency protection (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.FRPTRC2
4008
250.08
.Str.general
START
Stage 2 start
1=Start
4009
250.09
.mcd
LD0.FRPTOF2
Overfrequency
4010
250.10
.Op.general
OPR_OFRQ
Operate
1=Operate
4011
250.11
.mcd
LD0.FRPTUF2
Underfrequency
4012
250.12
.Op.general
OPR_UFRQ
Operate
1=Operate
4013
250.13
.mcd
LD0.FRPFRC2
Frequency gradient
4014
250.14
.Op.general
OPR_FRG
Operate
1=Operate
4015
250.15
.mcd
Section 2
1MRS757822 B
Modbus data mappings
30
Recloser Protection and Control RER615
Point List Manual