![ABB Relion RER615 Modbus Point List Manual Download Page 32](http://html.mh-extra.com/html/abb/relion-rer615/relion-rer615_modbus-point-list-manual_2828032.webp)
2.3.24
LD0.PDNSPTOC1 Phase discontinuity protection (1)
Table 27:
LD0.PDNSPTOC1 Phase discontinuity protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PDNSPTOC1
2952
184.08
.Str.general
START
Stage start
1=Start
2953
184.09
.mcd
2954
184.10
.Op.general
OPERATE
Stage operate
1=Operate
2955
184.11
.mcd
2.3.25
LD0.ROVPTOV1 Residual overvoltage protection (1)
Table 28:
LD0.ROVPTOV1 Residual overvoltage protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.ROVPTOV1
3168
198.00
.Str.general
START
General start
1=Start
3169
198.01
.mcd
3170
198.02
.Op.general
OPERATE
General operate
1=Operate
3171
198.03
.mcd
2.3.26
LD0.ROVPTOV2 Residual overvoltage protection (2)
Table 29:
LD0.ROVPTOV2 Residual overvoltage protection (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.ROVPTOV2
3172
198.04
.Str.general
START
General start
1=Start
3173
198.05
.mcd
3174
198.06
.Op.general
OPERATE
General operate
1=Operate
3175
198.07
.mcd
2.3.27
LD0.PHPTUV1 Phase undervoltage protection (1)
Table 30:
LD0.PHPTUV1 Phase undervoltage protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHPTUV1
3138
196.02
.Str.general
START
General start
1=Start
3139
196.03
.mcd
3140
196.04
.Str.phsA
phsA start
1=Start
3141
196.05
.mcd
Table continues on next page
Section 2
1MRS757822 B
Modbus data mappings
26
Recloser Protection and Control RER615
Point List Manual