OK
ALARM
RESET
LEDx
Signal
NOT
GUID-2AE4D47A-2BBD-4422-A81C-CF2EB7473379 V1 EN
Figure 3:
Signal wired to both OK and ALARM inputs – inverted to the other
If the OK and ALARM inputs are wired to separate indication
signals, the LED will have three legal states and cannot be
expressed with one bit only. In this case, it is possible to combine
this LED bit interpretation with the corresponding value from the
other LED state interpretation.
OK
ALARM
RESET
LEDx
Signal 1
Signal 2
GUID-051741E8-4D66-412C-BA0A-0B849B5E58F2 V1 EN
Figure 4:
Separate signals wired to OK and ALARM inputs
Table 82:
LD0.LEDGGIO1 Indication LED states Color1/Color2
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.LEDGGIO1
3520
220.00
.ISCSO1.stVal
-
LED 1 state
0/1=Color1/2
3521
220.01
.ISCSO2.stVal
-
LED 2 state
0/1=Color1/2
3522
220.02
.ISCSO3.stVal
-
LED 3 state
0/1=Color1/2
3523
220.03
.ISCSO4.stVal
-
LED 4 state
0/1=Color1/2
3524
220.04
.ISCSO5.stVal
-
LED 5 state
0/1=Color1/2
3525
220.05
.ISCSO6.stVal
-
LED 6 state
0/1=Color1/2
3526
220.06
.ISCSO7.stVal
-
LED 7 state
0/1=Color1/2
3527
220.07
.ISCSO8.stVal
-
LED 8 state
0/1=Color1/2
3528
220.08
.ISCSO9.stVal
-
LED 9 state
0/1=Color1/2
3529
220.09
.ISCSO10.stVal
-
LED 10 state
0/1=Color1/2
3530
220.10
.ISCSO11.stVal
-
LED 11 state
0/1=Color1/2
3531
220.11
<reserved>
0
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
49
Point List Manual