Table 19. Environmental conditions
Description
Value
Operating temperature range
-25...+55ºC (continuous)
Short-time service temperature range
-40...+85ºC (<16h)
1)2)
Relative humidity
<93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
Up to 2000 m
Transport and storage temperature range
-40...+85ºC
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For IEDs with an LC communication interface the maximum operating temperature is +70 ºC
Table 20. Environmental tests
Description
Type test value
Reference
Dry heat test (humidity
<50%)
• 96 h at +55ºC
• 16 h at +85ºC
1)
IEC 60068-2-2
Dry cold test
• 96 h at -25ºC
• 16 h at -40ºC
IEC 60068-2-1
Damp heat test, cyclic
• 6 cycles (12 h + 12 h) at
+25°C…+55°C, humidity >93%
IEC 60068-2-30
Storage test
• 96 h at -40ºC
• 96 h at +85ºC
IEC 60068-2-48
1) For IEDs with an LC communication interface the maximum operating temperature is +70
o
C
Motor Protection and Control