![ABB RELION REM615 Product Manual Download Page 23](http://html1.mh-extra.com/html/abb/relion-rem615/relion-rem615_product-manual_3368657023.webp)
Table 12. Double-pole power output relays with TCS function
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit
time constant L/R<40 ms, at 48/110/220 V
DC (two contacts connected in series)
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Trip-circuit supervision (TCS):
• Control voltage range
20...250 V AC/DC
• Current drain through the supervision
circuit
~1.5 mA
• Minimum voltage over the TCS contact
20 V AC/DC (15...20 V)
Table 13. Single-pole power output relays
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit
time constant L/R<40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
Table 14. Front port Ethernet interfaces
Ethernet
interface
Protocol
Cable
Data transfer
rate
Front
TCP/IP
protocol
Standard Ethernet CAT 5 cable with
RJ-45 connector
10 MBits/s
Motor Protection and Control
1MRS756890 D
REM615
Product version: 3.0
Issued: 2010-06-29
ABB
23
Summary of Contents for RELION REM615
Page 1: ...Relion 615 series Motor Protection and Control REM615 Product Guide ...
Page 69: ...69 ...
Page 70: ......
Page 71: ......