Table 31. Non-directional earth-fault protection (EFxPTOC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the current
measured: f
n
±2 Hz
EFLPTOC
±1.5% of the set value or ±0.002 x I
n
EFHPTOC
and
EFIPTOC
1)
±1.5% of set value or ±0.002 x I
n
(at currents in the range of 0.1…10 x I
n
)
±5.0% of the set value
(at currents in the range of 10…40 x I
n
)
Start time
2)3)
Minimum
Typical
Maximum
EFIPTOC
1)
:
I
Fault
= 2 x set
Start
value
I
Fault
= 10 x set
Start
value
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
EFHPTOC and
EFLPTOC:
I
Fault
= 2 x set
Start
value
22 ms
24 ms
25 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
4)
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n x f
n
, where n = 2, 3, 4, 5,
…
Peak-to-Peak: No suppression
1) Not included in REM615
2)
Measurement mode
= default (depends on stage), current before fault = 0.0 x I
n
, f
n
= 50 Hz, earth-fault current
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
3) Includes the delay of the signal output contact
4) Maximum
Start value
= 2.5 x I
n
,
Start value
multiples in range of 1.5 to 20
Motor Protection and Control
1MRS756890 D
REM615
Product version: 3.0
Issued: 2010-06-29
34
ABB