Table 46. Motor load jam protection (JAMPTOC) main settings
Parameter
Function
Value (Range)
Step
Operation
JAMPTOC
Off
On
-
Start value
JAMPTOC
0.10...10.00 x I
n
0.01
Operate delay time
JAMPTOC
100...120000 ms
10
Table 47. Motor start-up supervision (STTPMSU)
Characteristic
Value
Operation accuracy
Depending on the frequency of the current
measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 x I
n
Start time
1)2)
Minimum
Typical
Maximum
I
Fault
= 1.1 x set
Start
detection A
27 ms
30 ms
34 ms
Operate time accuracy
±1.0% of the set value or ±20 ms
Reset ratio
Typical 0.90
1) Current before = 0.0 x I
n
, f
n
= 50 Hz, overcurrent in one phase, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
Table 48. Motor start-up supervision (STTPMSU) main settings
Parameter
Function
Value (Range)
Step
Motor start-up A
STTPMSU
1.0...10.0 x I
n
0.1
Motor start-up time
STTPMSU
1...80.0 s
1
Lock rotor time
STTPMSU
2...120 s
1
Operation
STTPMSU
Off
On
-
Operation mode
STTPMSU
IIt
IIt, CB
IIt & stall
IIt & stall, CB
-
Restart inhibit time
STTPMSU
0...250 min
1
Motor Protection and Control
1MRS756890 D
REM615
Product version: 3.0
Issued: 2010-06-29
ABB
43