1.
Right click on the IED in the plant structure and select
Signal Monitoring.
2.
Click on the
List View tab.
3.
Click
Forcing Session in the menu IED/Start Forcing.
IEC15000023 V1 EN-US
4.
Click
Start editing signal value for forcing on the tool bar.
IEC15000024 V1 EN-US
The Signal Monitoring menu changes and indicates the forcing values that can be edited.
IEC15000025 V1 EN-US
5.
Select and edit the values.
6.
Click
Acknowledge and send.
IEC15000026 V1 EN-US
This commits the values to the IED and exits the editing session.
7.
Click
Cancel to abort the changes and revert back to actual IED values.
IEC15000032 V1 EN-US
1MRK 502 067-UEN B
Section 11
Testing IED operation
93
Commissioning manual