The expected value depends on whether definite or inverse time was selected.
7.
Set the polarizing voltage to zero and increase until the boolean output signal UNREL is
activated, which is visible in the Application Configuration in PCM600 when the IED is in
online mode. Compare the voltage with the set value
UNRel> .
8.
Continue to test another function or complete the test by setting the test mode to
Off.
Operate area
ROADir
IEC06000650_2_en.vsd
=
o
0
RCADir
0
3
I
j
0
3
×
j
I cos
-
=
0
3
ref
U
U
IEC06000650 V2 EN-US
Figure 57: Characteristic with ROADir restriction
Section 12
1MRK 502 067-UEN B
Testing functionality by secondary injection