Table 25:
Test points for phase-to-earth loop L3-E (Ohm/loop)
Test point
Value
Comments
1
X
[X1+XN]
XN=(X
0
-X
1
)/3
R
0
2
X
0
R
RLdFw
3
X
0.85·[X1+XN]
R≈0.491·(X1+XN)+RFFwPE
R
0.85·[X1+XN]·1/tan(60°)+RFFwPE
4
X
0.85·[X1+XN]
R
-0.85·[X1+XN]·
tan (AngNegRes-90°)
5
X
RFFwPE·tan (ArgLd)
R
RFFwPE
6
X
-0.5·RLdFw·tan (ArgDir)
R
0.5·RLdFw
The table showing test points for phase-to-earth loops is used together with figure
Table 26:
Test points for phase-to-phase loops L1–L2
Test point
Value
Comments
1
X
X1
R
0
2
X
0
R
RLdFw
3
X
0.85·X1
R=0.491·X1+0.5 RFFwPP
R
0.85·X1·1/tan(60°)+0.5 RFFwPP
4
X
0.85·X1
R
-0.85·X1·tan (AngNegRes-90°)
5
X
0.5·RFFwPP·tan (ArgLd)
R
0.5·RFFwPP
6
X
-0.5·RLdFw·tan (ArgDir)
R
0.5·RLdFw
The table showing test points for phase-to-phase loops is used together with figure
10.4.6.1
Measuring the operating limit of set values
Procedure:
Section 10
1MRK 506 355-UEN A
Testing functionality by secondary injection
106
Line distance protection REL670 2.1 IEC
Commissioning manual