Section 3
REG615 standard configurations
3.1
Standard configurations
REG615 is available with three alternative standard configurations. The standard
signal configuration can be altered by means of the signal matrix or the graphical
application functionality of the Protection and Control IED Manager PCM600.
Further, the application configuration functionality of PCM600 supports the creation
of multi-layer logic functions using various logical elements, including timers and
flip-flops. By combining protection functions with logic function blocks, the relay
configuration can be adapted to user-specific application requirements.
The protection relay is delivered from the factory with default connections described
in the functional diagrams for binary inputs, binary outputs, function-to-function
connections and alarm LEDs. Some of the supported functions in REG615 must be
added with the Application Configuration tool to be available in the Signal Matrix tool
and in the relay. The positive measuring direction of directional protection functions
is towards the busbar.
Table 9:
Standard configurations
Description
Std. conf.
Interconnection protection for distributed power generation
A
Generator protection with 100% stator earth-fault protection
C
Generator protection with generator differential and directional overcurrent protection and
synchro-check
D
Table 10:
Supported functions
Function
IEC 61850
A
C
D
Protection
Three-phase non-directional overcurrent protection, low stage
PHLPTOC
1
1
Three-phase non-directional overcurrent protection, high stage
PHHPTOC
1
1
Three-phase non-directional overcurrent protection, instantaneous
stage
PHIPTOC
1
1
1
Three-phase directional overcurrent protection, low stage
DPHLPDOC
2
1
TR
Three-phase directional overcurrent protection, high stage
DPHHPDOC
1
1
TR
Three-phase voltage-dependent overcurrent protection
PHPVOC
1
1
Non-directional earth-fault protection, high stage
EFHPTOC
1
1
1
Directional earth-fault protection, low stage
DEFLPDEF
2
2
2
Directional earth-fault protection, high stage
DEFHPDEF
1
1
1
Transient/intermittent earth-fault protection
INTRPTEF
1
1)
Negative-sequence overcurrent protection
NSPTOC
2
Negative-sequence overcurrent protection for machines
MNSPTOC
2
2
Residual overvoltage protection
ROVPTOV
2
2
2