REJ 513
User’s Guide
ABB Substation Automation
Products and Systems
1MRS750613-MUM
58
3 Check
lists
Setting group 1
Variable
Group 1
(R, W, P)
Setting
range
Default
setting
Customer’s
setting
Start current of
stage I>
S41
0.30...5.00 x I
n
0.30 x In
Operate time or time
multiplier k of stage I>
S42
0.05...300 s
0.05 s /
0.05
Start current of
stage I>>
S43
0.30...35.0 x I
n
0.30 x In
Operate time of
stage I>>
S44
0.04...300 s
0.04 s
Checksum, SGF 1
S45
0...255
0
Checksum, SGF 2
S46
0...255
0
Checksum, SGF 3
S47
0...255
0
Checksum, SGB 1
S48
0...255
0
Checksum, SGR 1
S49
0...255
12
Checksum, SGR 2
S50
0...255
3
Checksum, SGR 3
S51
0...255
12
Checksum, SGR 4
S52
0...255
3