ABB Substation Automation
Products and Systems
User’s Guide
REJ 513
1MRS750613-MUM
43
The last five recorded values can be read with parameters V11...V97. Event n denotes
the latest recorded value, n-1 the next one, and so forth.
Table 2.1.7.3-3 Recorded data
Recorded data
Event (R)
Value
n
n-1
n-2
n-3
n-4
Phase current I
L1
V11
V31
V51
V71
V91
0...50 x I
n
Phase current I
L2
V12
V32
V52
V72
V92
0...50 x I
n
Phase current I
L3
V13
V33
V53
V73
V93
0...50 x I
n
Start duration,
stage I>
V14
V34
V54
V74
V94
0...100 %
Start duration,
stage I>>
V15
V35
V55
V75
V95
0...100 %
Time stamp of
registered value, date
V16
V36
V56
V76
V96
YY-MM-DD
Time stamp of
registered value, time
V17
V37
V57
V77
V97
HH.MM;
SS.ms
Summary of Contents for REJ 513