REJ 513
User’s Guide
ABB Substation Automation
Products and Systems
1MRS750613-MUM
42
Recorded data
Parameters V1 and V2 indicate the number of starts of the protection stages,
parameter V3 indicates the stage that has caused an operation and parameter V4 the
operation.
Table 2.1.7.3-2 Parameters V1…V4
Recorded data
Parameter
R/W
Value
Number of starts of
stage I>
V1
R
0...255
Number of starts of
stage I>>
V2
R
0...255
Stage/phase that
caused operation
V3
R
1=I
L3
>
2=I
L2
>
4=I
L1
>
8=I
L3
>>
16=I
L2
>>
32=I
L1
>>
Operation indication
code
V4
R
0=no operation
1=starting of stage I>
2=tripping of stage I>
3=starting of stage I>>
4=tripping of stage I>>
5=tripping of CBFP unit
Summary of Contents for REJ 513