ProKiln GAC400
PROBE GAS SAMPLING SYSTEM | OI/GAC400-EN REV. A
… 3 Design and function
… Access permissions
By selecting ‘change password’ the following dialog will pop-up
and a new password can be created.
Figure 20: User dialog for changing the password
Default operation parameter settings
Parameter input cooling menu
Figure 21: Cooling menu
Parameter input Function
Default value
Start
Start temperature for hysteresis
control of water cooler fan
75 °C (167 °F)
Stop
Stop temperature for hysteresis
control of water cooler fan
70 °C (158 °F)
Flow
See
Parameter input Alarm setpoint
menu
on page 33 for alarm limits for
water flow OK
80 l/min
(21.13 gal US/min)
Parameter input analysis menu
Figure 22: Analysis menu
Parameter input Function
Default value
Analyse Time
The time for each sampling period
before probe cleaning
15 min
Cleaning before
retraction
The number of cleanings to take place
before the retractor automatically
retracts the probe from the kiln and
inserts it back again
10 times
(Every 2,5 hours)