94
FEM630 |
ELECTROMAGNETIC FLOWMETER | OI/FEM630-EN REV. A
Menu / parameter
Description
Communication
. . .HART
Selection of submenu ‘...HART’ using .
. . .Modbus
Selection of submenu ‘...Modbus’ using .
. . .Profibus
Selection of submenu ‘...Profibus’ using .
8 . . .Operation
. . .Parameter descriptions
Menu: Communication
Communication / . . .HART
Device Address
Selection of HART device address.
Note
The HART protocol has provisions for creating a bus with up to 15 devices (1 to 15)).
If an address greater than 0 is set, the device operates in multidrop mode. The current output 31 / 32 / Uco is
fixed to 4 mA. HART communication takes place only through current output 31 / 32 / Uco.
Loop Current Mode
Selection of the operating mode for current output with HART communication.
• Multidrop Fixed
• Normal Signaling
HART Tag
Entry of a HART TAG number as unique identifier for the device.
Alphanumeric, a maximum of 8 characters, upper case only, no special characters.
HART Long Tag
Entry of a HART TAG number as unique identifier for the device.
Alphanumeric, maximum of 32 characters, ASCII
Only starting from HART version 7!
HART Descriptor
Entry of a HART descriptor.
Alphanumeric, a maximum of 16 characters, upper case only, no special characters.
HART Message
Display of the alphanumeric TAG number.
HART Manuf. ID
Display of the HART manufacturer ID. ABB = 26
HART Device ID
Display of the HART device ID.
HART Find
Select whether the transmitter must respond to the HART command 73 (Find Device).
• Off: The transmitter does not respond to command 73.
• Once: The transmitter responds once to command 73.
• Continuous: The transmitter always responds to command 73.
Last HART Command
Display of the most recently sent HART command.