95
FEM630 |
ELECTROMAGNETIC FLOWMETER | OI/FEM630-EN REV. A
Menu / parameter
Description
Communication / . . .Modbus
Address
Setting the Modbus device address (1 to 127).
IEEE Format
Selection of the byte order for the Modbus communication.
• Enabled: If the IEEE format is activated, the data words are sent in the ‘little endian’ format with the
lowest value word first.
• Disabled: If the IEEE format is deactivated, the data words are sent in the standard Modbus ‘bigendian’
format.
Factory setting: Enabled.
Baud Rate
Selection of the transmission speed (baud rate) for the Modbus communication.
Factory setting: 9600 baud.
Parity
Selection of the parity for the Modbus communication.
Factory setting: Odd.
Stop Bits
Selection of the stop bits for the Modbus communication.
Factory setting: One stop bit
Response Delay
Setting of the pause time in milliseconds after receiving a Modbus command. The device sends a response no
earlier than expiration of the set pause time.
Factory setting: 10 ms
8 . . .Operation
. . .Parameter descriptions
Communication / . . .Profibus
Address
Set the PROFIBUS DP® device address (1 to 126).
Ident Nr. Selector
Display the PROFIBUS DP® identification number
• 9700: 1xAI
• 9740: 1xAI + 1xTOT
• 3432: ABB-specific
Comm State
Display the PROFIBUS communication status.
• Offline: No PROFIBUS® communication.
• Stop: Bus active, device not active.
• Clear: Device is being initialized.
• Operate: Cyclic communication is active.
Baud Rate
Display the transmission speed (baud rate) for the PROFIBUS® communication.
The baud rate is automatically detected and does not need to be configured manually.
PB Manufacturer ID
Display the PROFIBUS DP® manufacturer ID
• 26: ABB