5 . . .Installation
Installing the transmitter in the remote
mount design
When selecting a location for the transmitter, consider the
following points:
• Observe the information concerning maximum ambient
temperature and IP rating on the name plate
• The location must be mostly free from vibration.
• The location must not be exposed to direct sunlight. If
necessary provide a sun screen on site.
• Do not up-scale the maximum signal cable length
between the transmitter and the sensor.
1
Drill mounting holes at mounting location.
2
Attach transmitter securely to the mounting location
using suited fasteners for the base material.
G11567
205 (8.07)
2x45 = 90
(2x1.77 = 3.54)
262 (10.31)
71 (2.8)
71 (2.8)
Ø 7 (0.28)
1
Hole pattern for mounting holes
Hole pattern for mounting holes
1
1
Figure 19 Mounting dimensions dual-compartment housing
Figure 20 Mounting dimensions single-compartment housing