Program features 23
Active power limitations
External active power limit
Inverter output power can be limited by writing a new value for maximum output power in
parameter
. The external power limit has ramps
.
Settings
Limitation after grid connection and after grid fault
Active power can be limited after grid connection and after grid fault. The limitation type is
selected with parameter
. The limitation can be set to be active
always, only after grid fault or never. There are different ramp rates for grid connections
and re-connections after grid faults. Limitation ramp starts from 0%. Ramp is defined
as% / min.
Settings
nominal power
of the inverter
130.71 Connect limit ramp
130.72 Grid fault ramp
not connected connected