92 Parameters
188.66
Overvoltage enable 2
Enables overvoltage protection.
0
0 ... 1
1 = 1
188.67
Overvoltage limit 2
Sets limit for overvoltage protection.
120
100 ... 200%
1 = 1
188.68
Overvoltage time 2
Sets trip time for overvoltage protection.
0 ms
0 ... 120 000 ms
1 = 1 ms
188.69
Overvoltage enable 3
Enables overvoltage protection.
0
0 ... 1
1 = 1
188.70
Overvoltage limit 3
Sets limit for overvoltage protection.
130
100 ... 200%
1 = 1
188.71
Overvoltage time 3
Sets trip time for overvoltage protection.
0 ms
0 ... 120 000 ms
1 = 1 ms
188.72
Sliding overvoltage enable Enables sliding overvoltage protection.
0
0 ... 1
1 = 1
188.73
Sliding overvoltage limit
Sets limit for sliding overvoltage protection.
120%
100 ... 200%
1 = 1%
188.74
Sliding overvoltage time
Sets trip time for sliding overvoltage protection.
100 ms
0 ... 60 000 ms
1 = 1 ms
188.80
Combinatory trip
Enables combinatory protection.
0
0 ... 1
1 = 1
188.81
Combinatory trip time
Sets trip time for combinatory protection.
100 ms
0 ... 60 000 ms
1 = 1 ms
188.84
Comb pos seq voltage limit Sets positive sequence voltage limit in percent of
nominal line-to-line AC voltage for combinatory
protection.
130%
0 ... 200%
1 = 1 %
188.85
Comb neg seq voltage limit Sets negative sequence voltage limit in percent of
nominal line-to-line AC voltage for combinatory
protection.
10%
0 ... 200%
1 = 1%
188.86
Comb underfrequency limit Sets limit for combinatory underfrequency
protection.
-5 Hz
-30 ... 0 Hz
1 = 1 Hz /
10 = 1 Hz
188.87
Comb overfrequency limit
Sets limit for combinatory overfrequency
protection.
5 Hz
0 ... 30 Hz
1 = 1 Hz /
10 = 1 Hz
188.110
Rate of change of freq
enable
Enables rate of change of frequency limit.
0
0 ... 1
1 = 1
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...