80 Parameters
174.20
Relative threshold
Sets the relative string current threshold value.
Below this value the relative difference detection
is disabled.
1 A
0 … 100 A
1 = 1 A /
10 = 1 A
174.22
Blown fuse detection
Enables the blown fuse detection. Requires a
fuse board to be installed.
Enable
Disable
0
Enable
1
174.23
Blown fuse tolerance
Sets blown fuse detection tolerance.
0.1 A
0 … 100 A
1 = 1 A /
10 = 1 A
174.24
Blown fuse active
boundary
Sets the blown fuse detection boundary. If mean
current of the corresponding input is below this
value, blown fuse detection is not enabled.
1 A
0 … 100 A
1 = 1 A /
10 = 1 A
174.30
Reverse input current
detection
Enables reverse input current detection.
Enable
Disable
0
Enable
1
174.31
Reverse input current limit Sets the reverse input current detection limit.
1 A
0 … 1.5 A
100 = 1 A
174.32
Reverse input current
delay
Sets the duration for how long the reverse input
current must be above the limit before indicating a
fault.
10 s
0 … 600 s
1 = 1 s
174.35
Reverse string current
threshold
Sets the activation power level in percent of the
nominal power for reverse string current
detection.
10%
0 … 100%
1 = 1%
174.36
Reverse string current
delay
Sets the duration for how long the reverse string
current must be above the limit before indicating a
warning.
Note
: Reverse string current detection is
available only in -SX model.
60 s
0 … 600 s
1 = 1 s
174.50
Current: [1]
Measured current of string 1.
-
-15 … 15 A
100 = 1 A
174.51
Current: [2]
Measured current of string 2.
-
-15 … 15 A
100 = 1 A
174.52
Current: [3]
Measured current of string 3.
-
-15 … 15 A
100 = 1 A
174.53
Current: [4]
Measured current of string 4.
-
-15 … 15 A
100 = 1 A
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...