102 Fieldbus interfaces
Setting up embedded fieldbus interface
Set up the inverter for embedded fieldbus communication from the communication menu
or with the parameters in the group
. Modbus RTU is enabled by
default. Set a unique node address for each inverter with the parameter
. Check also other communication settings including baud rate and parity. The new
settings will take effect once refreshed with the parameter
.
Parameter
is read only. For options, see parameter
Accessing inverter parameters
Configuration parameters of the PRO-33.0-TL inverter can be accessed through Modbus
holding registers. Holding registers are 16-bit, read/write registers. The table below
describes the holding registers of the inverter. Registers 0 through 68 are described in
detail in a separate table. Registers 100 through 65535 are accessed using an addressing
scheme defined by parameter
.
Data I/O registers, 0-68
The Data I/O registers are Modbus RTU holding registers that can be programmed to give
access to any of the internal configuration parameters of the inverter. Parameters can both
be read and written to by accessing these registers, both 16-bit or 32-bit formats are
supported. The Data I/O registers give the user the possibility to group a number of
internal configuration parameters, with mixed 16/32 bit length, into a contiguous array of
registers that can be read in one operation by the Modbus master.
The Modbus data I/O registers are programmed via configuration parameters in parameter
group 158, indexes 101 ... 169. Most of the Data I/O registers have default configurations
but these can easily be changed when/if needed.
The Data I/O registers have, by default, been set up to mirror internal configuration
parameters as described in the tables below.
Data I/O registers 0 ... 2 programmed for inverter control command:
Start address
End address
Description
0
68
Data I/O
69
88
Not used
89
99
Modbus error codes
100
65535
Read/write registers
Holding
register
FbEq (16b/32b),
scaling
Description
Mirrored inverter
parameter
Config
Parameter
Name
0
16b, 1 = 1
Inverter operation
189.01
158.101
Data I/O 1
1
16b, 1 = 1
External power limit
130.75
158.102
Data I/O 2
2
16b, 1 = 1
User Qref
124.01
158.103
Data I/O 3
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...