Parameters 55
130.66
P(f) release time
Sets the waiting time before releasing the power
limit. The timer is started after the frequency
drops below the release frequency.
0 s
0 … 600 s
1 = 1 s
130.67
P(f) release ramp
Sets the ramp that is used after releasing the
power limit.
10%/min
0 … 600%/min
1 = 1%/min
130.68
P(f) release ramp ref
Sets the P(f) limiter's release ramp reference.
Nominal
Nominal
Ramp reference is relative to nominal power.
1
Corner power
Ramp reference is relative to corner power.
2
Pdelta
Ramp reference is relative to corner power minus
release power.
3
130.69
P(f) activation delay
Sets the waiting time before the Active power
limitation function is activated.
Note
: Default setting is 0 ms except for Italy when
3000 ms is used.
0 ms
0...5000 ms
Time
1 = 1 ms
130.70
Connect limit type
Selects the active power ramping type after
connecting to grid.
Off
Off
No active power ramping after grid connection.
0
After grid fault
Power ramping is active only after grid fault.
1
Always
Power ramping is active always when connecting
to grid.
2
130.71
Connect limit ramp
Sets the active power ramp that is used after
connecting to grid.
10%/min
0 … 600%/min
1 = 1%/min
130.72
Grid fault ramp
Sets the ramp that is used in reconnection after
grid fault.
10%/min
0 … 600%/min
Ramp value.
1 = 1%/min
130.75
External power limit
Sets the active power limit. Parameter for
externally controlled power limit.
200%
0 … 200%
1 = 1%
130.76
P(U) limiter
Activates P(U) limitation function.
Disable
Disable
0
Enable
1
130.77
P(U) trigger level
Sets the voltage level where power limitation is
triggered.
110%
0 … 200%
1 = 1%
130.78
P(U) release level
Sets the voltage level where power limitation is
released.
110%
0 … 200%
1 = 1%
130.79
P(U) limit level
Sets the limited power level.
20%
0 … 100%
1 = 1%
130.80
P(U) limit ramp
Sets the ramp down after power limit triggering.
50%/min
0 … 100%/min
1 = 1%/min
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...