12 The LCD display panel
—
5 LCD settings
You can use the LCD module to access the
settings for each operating mode.
The available modes are displayed in the center
oval. Table 11 below shows the different display
name acronyms for each mode.
—
Table 11: LCD mode setting options
String Meaning
Setting Options
OPV
Output voltage
Voltage options are:
•
220V
•
230V
•
240V
OPF
Output frequency
Frequency options are:
•
50Hz
•
60 Hz
bYPA
Bypass status
•
Select 000 for
Bypass Disable.
•
Select 001 for
Bypass Enable.
• UPS will enter bypass mode
after several seconds if
Bypass Enable is selected.
• UPS will turn to no output
mode after several seconds
if Bypass Disable is selected.
MOdE
Operating mode
• UPS—Normal operating
mode
• ECO—High-efficiency
mode
• CVF—Converter mode
EbPN
External battery
pack number
•
Values are 000 or 009.
•
009 means there are 9
external battery packs.
bATT
Battery remaining
time
Battery time values are:
•
000—Battery remaining
time function is disabled
and will not display on LCD
in battery mode.
•
001—Battery remaining
time function is enabled,
and the time will display
(minutes or seconds) in
battery mode or battery
test mode. bATT will
display on LCD every 2s.
CHG
Charger current
•
3.0/6.0 for 1KL T
(3.0 stands for 3A charger)
•
1.5/3.0/4.5/6.0 for 2KL/3KL T
5 1 1
Navigating the LCD
To access settings mode on the LCD display
panel, press the “Enter” button for more than
1 second.
The above modes are displayed individually in the
center oval. You can cycle through each mode by
pressing and holding “Enter” and then pressing
“Select.”
—
5 1 LCD setting overview
—